–18–

5. Heating Mode Operation

The unit will operate according to the setting by the remote controller and the operation diagram is shown as
following.

Intake Air Temp.

Setting Temp.

(Compressor ON)

Setting Temp. -1

°C(1.8°F)

Indoor Fan Speed

Compressor

ON

OFF

ON

OFF

OFF

Hot

Start

minimum

10sec.

minimum

10sec.

minimum

10sec.

minimum

10sec.

OFF

A

A

OFF

LOW

LOW

Setting Temp. +1

°C(1.8°F)

(Compressor OFF)

Selecting

fan speed

Selecting

fan speed

• A point: The indoor pipe temperature to be less then 35°C(95.0°F) & Discharge air Temperature to be less than 29°C(84.2°F).

The indoor fan operates for minimum 10sec. even if falls lower than 34°C(93.2°F).

Low(V)

Stop(VI)

39

°C(102.2°F)

Discharge Air Temp.

Indoor Pipe Temp.

34

°C(93.2°F)

28

°C(82.4°F)

26

°C(78.8°F)

Selecting Fan Speed(IV)

Low(II)

Stop(I)

(Hot-Start Operating)

Heating Start

(Hot-Start Release Point)

Selecting Fan Speed(III)

During heating operation, the operating procedure of the indoor fan is as the following.

Step

Indoor fan speed

Pipe temp.

Air discharge temp.

Off

28 C(82.4°F)(Hot start operating)

Low

28 C(82.4°F)

< 39°C(102.2°F)

Selecting speed

28 C(82.4°F)

≥ 39°C(102.2°F)

Selecting speed

28 C(82.4°F)

> 34°C(93.2°F)

Low

26 C(78.8°F)

≤ 34°C(93.2°F)

Off

26 C(78.8°F)