LG LF300CP(LP-C303R20) User Manual

Page 19

Advertising
background image

–19–

6. Hot-Start Control

• The indoor fan stops until the evaporator piping temperature will be reached to 28°C(82.4°F).

• During heating operation, if piping temperatures fall below 26°C(78.8°F) fan stops.

• The operation diagram is as following.

7. Defrost Control

• Defrost operation is controlled by timer and sensing temperature of outdoor pipe.

• The first defrost starts only when the outdoor pipe temperature falls below -6°C(21.2°F) after 45 minutes passed

from starting of heating operation and more than.

• Defrost ends after 10 minutes pass from starting of defrost operation or when the outdoor pipe temperature rises

over 12°C(53.6°F) even if before 10 minutes.

• The second defrost starts only when the outdoor pipe temperature falls below -6°C(21.2°F) after 45 minutes pass

from ending of the first defrost and more than.

INDOOR PIPE

TEMP.

INDOOR FAN

SPEED

Selecting

fan speed

OFF

OFF

LOW

1min

Maximum

COMPRESSOR

ON

28

°C(82.4°F)

26

°C(78.8°F)

More than 45 minutes of

heating operation

Outdoor Pipe Temp.

Indoor Fan

Compressor

4-Way Valve

ON

ON

ON

ON

OFF

ON

OFF

HOT-

START

ON

ON

OFF

OFF

ON

12

°C(53.6°F)

(Defrost OFF)

-6

°C(21.2°F)

(Defrost ON)

Within

10 minutes

Defrost

Defrost

More than 45 minutes of

heating operation