Lennox Hearth Gas Stove User Manual

Page 13

Advertising
background image

1

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

f

lue

r

estriCtors

This stove requires a balanced flue to ensure proper com-

bustion. As such, flue restrictors may need to be installed

depending on the vent configuration of your stove. The

drawings on the following page show all the allowable

pipe configurations for the Vision™ gas stove. To properly

install the flue restrictor, find your pipe configuration in the

drawings on the following page and note which restrictor

setting is recommended. The flue restrictor is shipped in

the firebox of your stove. To install the restrictor, see Figure

18. Remove the two 5/32” allen head screws (A below).

Using pliers, repeatedly bend the unwanted portion of the

flue restrictor and discard. Install the flue restrictor using

the two 5/32” allen head screws according to the diagram

below. Install the flue restrictor screws in their original holes

in the top of the firebox. Restrictor positions are based on

tests run in a laboratory.

Storm Collar

Vertical Termination

Cap

Ceiling Firestop

Framing 10”x 10”

Roof - Maintain 1”

Clearance to

Combustibles

Pipe

Length

Flashing

Hand break to remove

unwanted restrictor

Light Obstructor

(only used for Vision25 w/short

horizontal run & no flue restrictor)

Position 1

Flue Restrictor

Position 3

Position 2

A

v

ertiCal

v

ent

i

nstallation

Important Notes

1. All vertically terminated vent installations use 6-5/8”x 4”

Security™ Secure Vent™ pipe*.

2. If the vent passes through a ceiling or floor, a firestop

- Simpson #963 or Security #SV4BF - is required.

3. If the vent passes through the roof, a roof flashing -

Simpson #943 or 943S or Security #SV4FA or SV4FB

- and storm collar - Simpson #953 or Security #SV4FC

- are required.

4. A 1-inch clearance from the vent pipe to combustible

materials must be maintained.

5. A maximum of either two 45º elbows or two 90º elbows

may be used. See page 14 for allowable offsets.

6. The maximum system height is 30 feet and the minimum

is 10 feet.

14” Snorkel

min 12”

Figure 17

Figure 1

Figure 18