Gas line installation – Lennox Hearth Gas Stove User Manual

Page 16

Advertising
background image

1

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Gas Line Installation

This stove must be connected to the gas line in accordance

with local codes and/or the National Fuel Gas Code, ANSI

Z223.1 (In Canada, the current CAN/CSA B149.1 installation

code). The gas line screws into the gas valve at the back

of the stove 2-1/2” in from the left side of the stove and 8-

1/2”up from the base of the unit. After connecting the gas

line, all joints in the line and connections at the valve should

be checked for leaks.. After connecting the gas line, all joints

in the line and connections at the valve should be checked

for leaks using a gas leak test solution.

g

as

p

ressure

r

equirements

A MAJOR CAUSE OF OPERATING PROBLEMS WITH GAS

APPLIANCES IS IMPROPER GAS PRESSURE!

The most important item to check during the initial

installation and the first thing to check when operating

problems occur is gas pressure! This appliance will

not function properly unless the required gas pressure

is supplied. See the table on this page for gas pressure

requirements.

Two pressure taps are provided on the stove’s valve to check

gas pressures. To access the taps, remove the two socket

head screws from the valve control panel. The taps are

located below the on/off/pilot knob. The left tap is the inlet

(supply) pressure side. To check inlet pressure (with the stove

burning) insert a small flat-bladed screwdriver into the tap

and turn a half-turn counter-clockwise. Cover the tap with

the line from the manometer and check the pressure. Close

the tap gently but securely after completing the check. The

manifold (outlet) tap is to the right of the inlet tap. To check

manifold pressure (with the stove burning at the high burn

setting) insert a small flat-bladed screwdriver into the tap

and turn a half-turn counter-clockwise. Cover the tap with

the line from the manometer and check the pressure. Again,

close the tap gently but securely after completing the check.

Check the taps for gas leaks with a gas leak test solution

(retighten if necessary).

If the pressure is not sufficient, make sure the gas supply line

is large enough, the supply regulator improperly adjusted,

and the total gas load for the residence does not exceed the

amount supplied.

The appliance and its individual shut off valve must be

disconnected from the gas supply piping system during

any pressure testing of that system at test pressures in

excess of 1/ psig.

The appliance must be isolated from the gas supply piping

system by closing its individual manual shut-off valve

during any pressure testing of the gas supply piping system

at test pressures equal to or less than 1/ psig. Check

with your gas supplier or plumber.

lp

and

n

atural

g

as

s

upplies

Your Vision™ gas stove is equipped from the factory for

use with natural gas only as specified on the Safety / Listing

label attached to the appliance. This appliance can only be

operated using propane gas (LP) if a certified fuel conver-

sion kit provided by Lennox Hearth Products is installed by

a qualified service technician.

Also check the orifice size on the label on the igniter bracket.

It must be the correct size for the fuel and altitude.

Do not run propane tank dry. Running the tank dry may

cause a hazardous condition due to pressure drop in

empty tank.

Solid fuel is NOT to be used with this unit.

Fuel

Type

Inlet Pressure

Manifold Pressure

Desired Minimum Maximum

On Hi

Fire

On Lo

Fire

Natural

Gas

7" WC

5" WC

10.5" WC

.5" WC 1.8" WC

LP Gas

11" WC 11" WC

1" WC

10" WC

.0” WC