Lennox Hearth ADAGIO-EN User Manual

Page 15

Advertising
background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

15

Figure 17

10-1/2" Min.

(267 mm)

10-1/2" Min.

(267 mm)

Ceiling Framing

Plumb Bob

To attach a vent component to the appliance

collar, align the dimpled end over the collar,

adjusting the radial alignment until the four

locking dimples are aligned with the inlet of

the four inclined channels on the collar (refer to

Figure 18). Push the vent component against

the collar until it fully engages, then twist the

component clockwise, running the dimples

down and along the incline channels until they

seat at the end of the channels.

The unitized design of the Secure Vent com-

ponents will engage and seal both the inner

and outer pipe without the need for sealant or

screws. If desired a #6 x 1/2" screw may be

used at the joint, but it is not required as the

pipe will securely lock when twisted.

C. Attach vent components to each other - Other

vent sections may be added to the previously

installed section in accordance with the require-

ments of the vertical vent figures and tables.

To add another vent component to a length of

vent run, align the dimpled end over the inclined

channel end of the previously installed section,

adjusting the radial alignment until the four lock-

ing dimples are aligned with the inlets of the four

incline channels of the previous section.

B. Attach vent components to appliance

- Secure Vent SV4.5 direct-vent system compo-

nents are unitized concentric pipe components

featuring positive twist lock connections (see

Figure 18).

All of the appliances covered in this document

are fitted with collars having locking inclined

channels. The dimpled end of the vent compo-

nents fit over the appliance collar to create the

positive twist lock connection.

Align the dimple (four places) of the

upper vent section with the opening

of the locking incline channel on the

lower vent section or appliance col-

lar. Twist vent component clockwise

to engage and seal until arrow and

dimple align.

Dimple

Locking Incline

Channel

Connected Vent

Sections

Arrow

Arrow

Appliance Collar or

Vent Section

Figure 18

Push the vent component against the previous

section until it fully engages, then twist the

component clockwise running the dimples down

and along the incline channels until they seat at

the end of the channels. This seating position

is indicated by the alignment of the arrow and

dimple as shown in Figure 18.

D. Install firestop/spacer at ceiling - When

using Secure Vent, use SV4.5VF firestop/spacer

at ceiling joists; when using Secure Flex, use

SF4.5VF firestop/spacer. If there is living space

above the ceiling level, the firestop/spacer must

be installed on the bottom side of the ceiling.

If attic space is above the ceiling, the firestop/

spacer must be installed on the top side of

the joist. Route the vent sections through the

framed opening and secure the firestop/spacer

with 8d nails or other appropriate fasteners at

each corner. Remember to maintain 1" (25

mm) clearance to combustibles, framing

members, and attic or ceiling insulation

when running vertical chimney sections. Attic

insulation shield may be used to obtain the

required clearances indicated here (order

H3907, SV4.5ARSA, Attic insulation shield

with adjustable height from 12"-22"). See

installation accessories table on Page 32.

The gap between the vent pipe and a vertical

firestop can be sealed with non-combustible

caulking.

E. Support the vertical vent run sections -

Note - Proper venting support is very important.

The weight of the vent must not be supported

by the fireplace in any degree.

Support the vertical portion of the venting

system every 8 feet (2.4m) above the fireplace

vent outlet.

Figure 19

Blocking

Support Straps

(Plumber's tape)

8 feet (2.4 m)

Maximum

1 inch (25.4

mm) minimum

clearance to

combustibles

Roof Framing

Vertical (Offset) Installation

Analyze the vent routing and determine the

quantities of vent sections and number of el-

bows required. Refer to Vertical Vent Figures

and Tables on Page 17 to select the type of

vertical installation desired. Vent sections are

available in net lengths of 4-1/2" (114 mm),

10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2"

(876 mm) and 46-1/2" (1181 mm). Refer to the

Vent Section Length Chart on Page 14 for an

aid in selecting length combinations. Elbows are

available in 90° and 45° configurations. Refer

to Figure 20 for the SV4.5E45 and SV4.5E90

elbow dimensional specifications.

Where required, a telescopic vent section

(SV4.5LA) may be used to provide the installer

with an option in installing in tight and confined

spaces or where the vent run made up of fixed

length pieces develops a joint in a undesirable

location, or will not build up to the required

length. The SV4.5LA Telescopic Vent Section

has an effective length of from 1-1/2" (38 mm)

to 7-1/2 " (191 mm). The SV4.5LA is fitted with

a locking inclined channel end (identical to a

normal vent section component) and a plain end

with 3 pilot holes. Slip the plain end over the

locking channel end of a standard SV4.5 vent

component the required distance and secure

with three screws.

Maintain a minimum 1" (25 mm) clear-

ance to combustible materials for all

vertical vent components. Clearances for

all horizontal vent components are 3"

(76 mm) on top, 1" (25 mm) on sides and 1"

(25 mm) on the bottom.

A. Frame ceiling opening - Use a plumb line

from the ceiling above the appliance to locate

center of the vertical run. Cut and/or frame an

opening, 10-1/2" x 10-1/2" (267 mm x 267

mm) inside dimensions, about this center mark

(Figure 17).

Advertising
This manual is related to the following products: