Lennox Hearth WHITFIELD 30 FS-2 User Manual

Page 16

Advertising
background image

16

Wall Straps
Required Every
4 feet Minimum

Standard Vertical Installation Confi gurations

Models: Profi le

®

20 FS-2 and Profi le 30 FS-2

These free-standing models may be connected to an existing fl ue or by
installing listed type “PL” vent pipe. If a liner is run all the way to the
top of the existing chimney, the existing fl ue should be sealed with a
steel plate. Start a vertical run with a Tee at the back of the stove. Other
options are illustrated below.

Preferred Installation – Vertical Vent Through the Roof

This venting confi guration allows for the best stove performance. The
vertical pipe promotes natural draft and with the chimney inside the
dwelling, the fl ue gases stay warm, thus rising at a consistent rate.

Note: See Page 12 for Vent Termination Requirements

3”

Min.

Clean-

out

Tee

Flashing

Listed Rain Cap

Extend Pipe to the Top
if Existing Chimney is
Corroded or Damaged

3”

Min.

Pipe Increaser

Existing
Chimney Pipe

Optional
Clean-Out
Access Door

Optional Complete
Liner and Listed
Termination Cap

Figure 25 - Exterior Vertical Vent

Figure 27 - Vertical Vent Into a Masonry Flue

Figure 26 - Vertical Vent Through the Roof

Figure 28 - Interior Vertical Vent into Class A Chimney

Advertising
This manual is related to the following products: