Gas pressure adjustment, High altitude information, Other unit adjustments and operation – Lennox International Inc. G24-200 User Manual

Page 35

Advertising
background image

Page 35

Gas Pressure Adjustment

Gas Flow (Approximate)

1− Operate unit at least 15 minutes before checking gas

flow. Determine the time in seconds for two revolu-
tions of gas through the meter. (Two revolutions as-
sures a more accurate time.) A portable LP gas meter
(17Y44) is available for LP applications.

2− Divide the number of seconds by two and compare

to the time in table 11. If manifold pressure is correct
and rate is incorrect, check gas orifices for proper size
and restriction.

3− Remove temporary gas meter if installed.

NOTE− To obtain accurate reading, shut off all other gas
appliances connected to meter.

TABLE 11

GAS METER CLOCKING CHART

Unit

Seconds for One Revolution

Unit

Input

Natural

LP

Input

Rate

(Btuh)

1 cu ft

Dial

2 cu ft

Dial

1 cu ft

Dial

2 cu ft

Dial

75,000

48

96

120

240

125,000

29

58

72

144

130,000

28

55

69

138

235,000

15

31

38

77

260,000

14

28

35

69

470,000

8

15

19

38

Natural−1000 btu/cu ft LP−2500 btu/cu ft

Note: Table assumes standard temperature (60°F), pressure

(30in.Hg.), and fuel heating values (Btuh/Ft.

3

). Apply pressure

corrections in altitudes above 2000 ft.

Gas Pressure

1 − Check the gas line pressure with the unit (both heat sec-

tions) firing at the high heat input rate. A minimum of 4.5
in. w.c. for natural gas should be maintained.

2 − After the line pressure has been checked and ad-

justed, check the high heat regulator pressure on both
gas valves. See figure 20 for gas pressure adjustment
screw location. The low heat setting is factory-set and
is not field-adjustable. The high heat manifold pres-
sure settings are given in table 12.

TABLE 12

MANIFOLD GAS PRESSURES (HIGH HEAT)

ALTITUDE

feet (m)

GAS

FUEL

MANIFOLD PRESSURE

in. w.c. (kPa)

0 − 2000 (0 − 610)

Natural

3.5 (0.87)

2000 − 4500 (610 − 1372)

Natural

3.5 (0.87)

4500 − 7500* (1372 −

2286)

Natural

3.2 (0.80)

*In Canada, certification for installation at altitudes over
4500 feet (1372m) above sea level is the jurisdiction of the
local authorities.

High Altitude Information

In Canada, certification for installation at altitudes over
4500 feet (1372m) above sea level is the jurisdiction of the

local authorities.

See table 12 for the correct high heat manifold pressures to
be maintained for natural gas.

Check the gas line pressure with the unit (both heat sections)
firing at high heat input rate The minimum pressure as
shown on the nameplate for natural gas must be main-
tained.

No orifice change is required. No pressure switch change
is required.

Other Unit Adjustments and Operation

Primary (S10 and S99) Limits

Each heat section has a primary limit located on the heat-
ing compartment vestibule panel. These limits are facto-
ry set and do not require field adjustment.

Flame Rollout Switches (S47 and S69)

Each heat section has a manually reset flame rollout switch.
Each switch is located on the burner top plate. If tripped, a
check for adequate combustion air should be made before

resetting. The switches are non-adjustable.

Combustion Air Pressure Switches (S18 and S45)

Each heat section has a combustion air pressure switch lo-
cated on the heating compartment vestibule panel. Each
switch checks for proper combustion air blower operation
before allowing ignition trial. The switches are factory set
and require no field adjustment.

Blower Motor Controls (K25 Circuit Board),
(K20 Relay), (K123 Relay) and (K36 Relay)

When the gas valves are powered, the blower motor starts
after a delay of 45 seconds. When the gas valves lose pow-

er because the thermostat demand is satisfied, the blower
motor remains running for 150 seconds. These timings are
programmed into the K25 control board and are non-ad-
justable. The board is located in the control box.

If abnormal furnace operation causes either high limit (S10
or S99) to open, the relays K20, K123 and K36 maintain
blower operation until the limit(s) is reset.