Temperature Rise

Check the temperature rise and, if necessary, adjust the

blower speed to maintain the temperature rise within the
range shown on the unit rating plate.

Electro-mechanical Thermostat Heat Anticipation

In single-stage heat applications, set the heat anticipation
to 0.2 amps.
In two-stage heat applications, set the heat anticipation to
0.26 amps and install a field-provided resistor (150 ohm, 10

watt rating −Lennox part number P−8−6256) in parallel with
K13 relay coil.

Electrical

1 − Check all wiring for loose connections.

2 − Check for the correct voltage at the furnace (furnace

operating).

3 − Check amp-draw on blower motor.

Motor service factor amps
Nameplate __________Actual__________

Flue And Chimney

1 − Check flue pipe, chimney and all connections for tight-

ness and to make sure there is no blockage.

2 − Check unit for proper draft.

3 − Are pressure switches closed? Obstructed flue will

open pressure switches and cause unit to shut down.
Check flue and outlet for blockages.

4 − Reset manual flame rollout switches on burner box

covers.

Burner Flame Adjustment

The G24−200 burner flame is not adjustable; however, the
flame should be inspected at the beginning of each heating
season. If necessary, clean the burners. Burner flame

should be blue when burning natural gas. See figure 21.

BURNER FLAME

BURNER

FLAME

HEAT

EXCHANGER

TUBE

VEST

PANEL

FLAME APPEARS

BLUE IF BURNING

NAT. GAS.

FIGURE 21

Failure To Operate

If unit fails to operate check the following:

1 − Is the thermostat calling for heat?

2 − Are access panels securely in place?

3 − Is the main disconnect switch closed?

4 − Is there a blown fuse or tripped circuit breaker?

5 − Are the filters dirty or plugged? Dirty or plugged filters

will cause the limit controls to shut the unit off.

6 − Is gas turned on at the meter?

7 − Is the manual main shut-off valve open?

8 − Are the internal manual shut-off valves open?

9 − Are the unit ignition systems in lock out mode? If unit

locks out again, call serviceman to inspect unit for block-
ages.