Lennox International Inc. G24-200 User Manual

Page 41

Advertising
background image

Page 41

HEATING SEQUENCE OF OPERATION WITH TWO-STAGE THERMOSTAT CONTINUED

NORMAL HEATING MODE

ABNORMAL HEATING MODE

YES

HAS ROOM AIR TEMPERATURE CONTINUED

TO DROP BELOW THE THERMOSTAT"S

W2 SET POINT?

DETERMINE WHY AUTOMATIC-RESET

S10 (S99) HIGH LIMIT OPEN. K20, (K123), K36

RELAYS MAINTAIN BLOWER OPERATION.

IS THE S10 (S99) HIGH LIMIT CLOSED?

IS W1 DEMAND SATISFIED?

A3 (A12) LED OFF

YES

B6 (B15) COMBUSTION

AIR BLOWER OFF.

B3 SYSTEM BLOWERS OFF

AFTER 150 SEC DELAY.

NO

YES

NO

POWER FROM W2

ENERGIZES K19 RELAY

SECOND-STAGE OF GV1 (GV3)

GAS VALVE ENERGIZED (HIGH HEAT)

AFTER APPROXIMATELY 3 SEC.

IS W2 DEMAND SATISFIED?

YES

CLOSE SECOND-STAGE OF

GV1 (GV3) GAS VALVE AFTER

APPROXIMATELY 3 SEC. AND THEN

RETURN TO LOW HEAT OPERATION.

LED CODES

1 − ON NORMAL OPERATION WITH THERMOSTAT CALLING FOR HEAT.
2 − 0.5 SEC ON AND 2.5 SECS OFF IN IGNITION RETRY PERIOD.
3 − OFF NO POWER OR DETECTED FAULT.

FIRST-STAGE OF GV1 (GV3)

GAS VALVE CLOSES.

NOTE − IF ECONOMIZER INSTALLED, ECONOMIZER OPERATES WHEN BLOWER POWERED.

Advertising