Lennox International Inc. G24-200 User Manual

Page 43

Advertising
background image

Page 43

HEATING SEQUENCE OF OPERATION WITH SINGLE-STAGE THERMOSTAT CONTINUED

NORMAL HEATING MODE

ABNORMAL HEATING MODE

DETERMINE WHY AUTOMATIC-RESET

S10 (S99) HIGH LIMIT OPEN. K20, (K123), K36

RELAYS MAINTAIN BLOWER OPERATION.

IS THE S10 (S99) HIGH LIMIT CLOSED?

IS W1 DEMAND OF

THERMOSTAT SATISFIED?

A3 (A12) LED OFF

YES

B6 (B15) COMBUSTION

AIR BLOWER OFF.

B3 SYSTEM BLOWERS OFF

AFTER 150 SEC DELAY.

NO

YES

NOTE − IF ECONOMIZER INSTALLED, ECONOMIZER OPERATES WHEN BLOWER POWERED.

LED CODES

1 − ON NORMAL OPERATION WITH THERMOSTAT CALLING FOR HEAT.
2 − 0.5 SEC ON AND 2.5 SECS OFF IN IGNITION RETRY PERIOD.
3 − OFF NO POWER OR DETECTED FAULT.

SECOND-STAGE OF GV1 (GV3)

GAS VALVE CLOSES AFTER

APRROXIMATELY 3 SEC. AND
THEN FIRST-STAGE CLOSES.

Advertising