Lennox International Inc. G24-200 User Manual

Page 42

Advertising
background image

Page 42

HEATING SEQUENCE OF OPERATION WITH SINGLE-STAGE THERMOSTAT

NORMAL HEATING MODE

ABNORMAL HEATING MODE

YES

YES

POWER ON

IS THE S47 (S69) ROLLOUT SWITCH CLOSED?

B6 (B15) COMBUSTION AIR BLOWER

PREPURGE FOR 30 SECS.

DETERMINE WHY AUTOMATIC-RESET

S10 (S99) HIGH LIMIT OPEN.

YES

NO

NO

8 SEC TRIAL FOR IGNITION − START IGNITION

TRAIL, GV1 (GV3) GAS VALVE OPENS ON LOW

HEAT AND AFTER A 3 SEC. DELAY OPENS ON

HIGH HEAT. IS FLAME SENSED WITHIN 8 SECS?

CONTINUED NEXT PAGE

THERMOSTAT CALLS FOR HEAT

(W1 ENERGIZED)

K13 AND K19 RELAY ENERIZED.

(W1 AND W2 OF FURNACE

TERMINAL STRIP JUMPERED.)

A3 (A12) IGNITION CONTROL LED ON.

IS THE S10 (S99) HIGH LIMIT CLOSED?

CHECK VENTING SYSTEM

OPERATION/BLOCKAGE BEFORE

RESETTING THE MANUALLY-RESET S47

(S69) ROLLOUT SWITCH.

IS THE B6 (B15) COMBUSTION

AIR BLOWER ON?

CHECK K13−1 CONTACT OPERATION AND

WIRING TO B6 (B15) COMBUSTION AIR

BLOWER?

NO

YES

IS THE S18 (S45) COMBUSTION AIR

BLOWER PROVING SWITCH CLOSED?

CHECK SENSING TUBE FOR BLOCKAGE

AND S18 (S45) SWITCH FOR PROPER

OPERATION.

NO

NO

GV1 (GV3) GAS VALVE CLOSED, SPARK

OFF. INCREMENT TRAIL REGISTER.

(DURING RETRY PERIOD LED FLASHES

.5 SEC. ON AND 2.5 SEC. OFF. ARE THE

THREE TRIALS COMPLETE?

LOCKOUT OCCURS. TO RESET A3 (A12) IGNITION

CONTROL MOVE THERMOSTAT SWITCH FROM

HEAT TO OFF TO HEAT.

K56 (K57) RELAY ENERGIZED. K25 CIRCUIT

BOARD ENERGIZED. SYSTEM BLOWERS ON

AFTER 45 SEC DELAY.

YES

CHECK BELT.

CHECK RELAYS.

YES

NO

YES

NOTE − THIS FURNACE FUNCTIONS WITH TWO INDEPENDENTLY CONTROLLED HEAT SECTIONS.

THE GRAY BOXES INDICATE COMPONENTS WHICH EFFECT BOTH HEAT SECTIONS SIMULTANEOUSLY.

NO

NO

FLAME SENSE OK?

YES

Advertising