3. Cooling Cycle Heavy Repair

3-1. The Heavy Repair Standards for Refrigerator with R134a Refrigerant

NOTE) Please contact Songso company on +82-53-554-2067 if you have inquiry on heavy repair special facility.

TROUBLE DIAGNOSIS

- 72 -

NO.

Items

Unit

Standards

Purposes

Remarks

1

Pipe and piping

Min.

Pipe:within 1 hour.

To protect

The opening time should be reduced to a

system opening time.

Comp:within

Moisture

half of the standards during rain and

10 minutes.

Penetration. rainy seasons (the penetration of water

Drier:within

into the pipe is dangerous).

20 minutes.

2

Welding.

Nitrogen

Weld under

To protect

- Refet to repair note in each part.

Pressure.

Nitrogen

oxide scale

- R134a refrigerant is more susceptible to

atmosphere

formation.

leaks than R12 and requires more care

(N

2

pressure:

during welding.

0.1~0.2 kg/cm

2

)

- Do not apply force to pipes before and

after welding to protect pipe from
cracking.

3

N

2

sealed parts.

Confirm N

2

Confirm air leaking

To protect

- In case of evaporator parts, if it doesn't

leak.

sounds when

moisture

noise when removing rubber cap blow

removing rubber

penetration.

dry air or N

2

gas for more than 1 min

cap.

use the parts.

Sound:usable
No sound:not usable

4

Refrigeration

Evacuation

Min.

More than

To remove

Cycle.

time

40 minutes.

moisture.

Vacuum

Torr

Below 0.03(ref)

Note:Only applicable to the model

degree

equipped with reverse flow protect
plate.

Vacuum

EA

High and low

Vaccum efficiency can be improved by

Pressure sides are

operating compressor during evacuation.

evacuated at the
same time for
models above 200

L

Vacuum

EA

Use R134a

To protect

The rubber pipes for R12 refrigerant shall

piping

exclusive

mixing of

be melted when they are used for R134a

manifold.

mineral and refrigerant(causes of leak).

ester oils.

Pipe

EA

Use R134a

To protect

coupler

cxclusive.

R12 Refri-

gerant mixing.

Outlet

R134a exclusive.

(Socket)

Plug

R134a exclusive

5

Refrigerant weighing.

EA

Use R134a

Do not mix

- Do not weight the refrigerant at too hot or

exclusively.

with R12

too cold an area.(25°C is adequate.)

Weighing

refrigerant.

- Use copper bombe

allowance:±5g

Socket:2SV Plug: 2PV R134a

Note:Winter:-5g

Note:Do not burn O-ring (rubber) during

Summer:+5g

welding.

6

Drier replacement.

-Use R134a exclusively

To remove

for R134a refrigerator the moisture

-Use R12 exclusively

from pipe.

for R12 refrigerator

-Replace drier whenever

repairing refrigerator
cycle piping.

7

Leak check.

-Do not use soapy

Detect

-Check oil leak at refrigerant leak area.

water for check.

refrigerant

Use electronic leak detector if oil leak is

it may be sucked

leak area.

not found.

into the pipe by.

-The electronic leak detector is very

sensitive to halogen gas in the air. It also
can detect R141b in urethane. Please
practice, therfore, many times before use.