Tvss series model, Surge suppression systems, Powersure medium exposure series — type lpm 100-2 – Liebert PanelGuard Extension User Manual

Page 11: Powersure medium exposure series — type lpm 160, Allowable range factory suggested size

Advertising
background image

Surge Suppression Systems

Installation, Operation and Maintenance Manual

9

Liebert TVSS Units SL-22085 Rev 2, 11/2006

7.

An external circuit breaker is not necessary for over-current protection for most units (LPL Units require a 30A or less circuit

breaker). However, it is recommended that the SPD be connected in series with a circuit breaker denoted in the tables below
(also indicated on the “Dimensional Information” pages in this manual). The SPD shall be connected in accordance with all
national and local electrical codes.

5. Connect black wires (line or phase) marked L1/A, L2/B or L3/C, the white wire (neutral) marked N, and the green wire (ground)

marked G, of the SPD using the wire range listed below. To yield the best performance of the SPD within the electrical
distribution system, keep all conductors as short as possible and avoid sharp bends.

If the SPD model is a Wye confi gured unit (4W+G),

and a Neutral connection is not available, please contact factory.

Surge Voltage Ratings. To obtain the suppression voltage ratings (SVRs), as obtained by Underwriters Laboratory, Incorporated,
in accordance with the Standard for Safety, Transient Voltage Surge Suppressors (TVSS), Standard 1449, Second Edition, dated August
15, 1996, marked on this product, the suggested wire size must be utilized to connect the unit to your facilities power grid.
Connections made with conductors other than the size provided may result in different SVRs.

6. Connection to Form ‘C’ contacts shall be with #18 – 22 AWG. The ratings of the Form ‘C’ contacts are 5 amps at 250 VAC

maximum with a power factor of 1.0. For additional information on Interceptor II connections, see page 15.

7. Apply power. The surge protector is fully operational when the GREEN LEDs on the modules and the front door of enclosure are

illuminated. If the GREEN LEDs are extinguished or a RED LED is illuminated, check to ensure that power is applied to the SPD.
If an abnormal indication is present, remove power to the SPD and contact Liebert/Emerson Network Power Surge Protection
at 1-800-288-6169 or 1-607-724-2484.

8. Periodically monitor the status of the LEDs. Reduced protection exists if the GREEN LEDs are extinguished or the RED LED is

illuminated. Please contact Liebert/Emerson Network Power Surge Protection at 1-800-288-6169 or 1-607-724-2484.

9. The protection modules in these SPDs may be replaceable, contact Liebert/Emerson Network Power Surge Protection for

replacement. (Note: ACV, LPM, & LPL units do not have replaceable modules).

TVSS

Series

Model #

Allowable Range

Factory Suggested Size

Circuit Breaker Size

Connection Wire Size

Circuit Breaker

Size

Connection

Wire Size

With Disconnect

Without Disconnect With Disconnect

Without Disconnect

Interceptor II

Hybrid Advantage

Type SS Series

LM Series

AccuVar

PowerSure LPM

SI016 – SI025
SI032 – SI050
SI060 – SI075

SI100

Hxxxxx111 (250kA)
Hxxxxx222 (320kA)
Hxxxxx333 (400kA)
Hxxxxx444 (750kA)

All Units

LM060 – LM080
LM100 – LM150
LM200 – LM250

All Units

LPM 100-2

LPM 160

N/A

15A – 150A

15A – 175 A

15A – 175A
15A – 175A
15A – 150A
15A – 175A
15A – 175A
15A – 175A

N/A

15A – 150A
15A – 175A
15A – 175A

N/A

N/A

N/A

15A – 175A

15A – 175A

15A – 175A

15A – 100A

15A – 30A

30 Amp

30 Amp or less

30 Amp Required

#14 – 1/O
#14 – 2/O
#14 – 2/O
#14 – 2/O
#14 – 1/O
#14 – 2/O
#14 – 2/O
#14 – 2/O

N/A

#14 – 1/O
#14 – 2/O
#14 – 2/O

N/A

N/A

N/A

#14 – 2/O

#14 – 2/O

#14 – 2/O

#14 – #2

#14 – #10

60 Amp
80 Amp
80 Amp

100 Amp

60 Amp
80 Amp
80 Amp
80 Amp
80 Amp
40 Amp
40 Amp

100 Amp

30 Amp

30 Amp

#6
#4
#4
#2
#6
#4
#4
#4
#4
#8
#8
#2

#10

#12 Provided

#12 Provided

PowerSure LPL

N/A

N/A

.31 (4X)

0.500

4.000

8.750

8.000

0.375

3.500

Service Panel

for Loads to

be Protected

Phase L3/C
Phase L2/B
Phase L1/A

Disconnect/Main

Breaker for Panel

Neutral Buss

Ground Buss

Dedicated

Disconnect

(Optional)

Installation, Operation and Maintenance Manual

20

Liebert TVSS Units SL-22085 Rev 2, 11/2006

Surge Suppression Systems

PowerSure Medium Exposure Series — Type LPM 100-2

0.375

6.750

0.500

2.000

6.000

Phase A Phase B Phase C

Service

.31 (4X)

3.000

4.000

Phase A Phase B Phase C

Service

Service Panel

for Loads to

be Protected

Phase L1/A

Phase L2/B

Phase L3/C

Disconnect/Main

Breaker for

Panel
Neutral Buss

Ground Buss

Dedicated

Disconnect

(Optional)

Unit is supplied from the

factory with a minimum

length of 18” of #12

wire for connection. It

is recommended that a

30A circuit breaker be

used for installation.

Unit is equipped with Summary

Alarm Contacts. The #18 wires

are designated as follows:

YELLOW = Normally Open
ORANGE = COMMON
BLUE = Normally Closed

PowerSure Medium Exposure Series — Type LPM 160

Unit is supplied from

the factory with a

minimum length

of 18” of #10 wire

for connection. It is

recommended that a

30A circuit breaker be

used for installation.

Liebert Interceptor II Printer S11 11