Surge suppression systems, Liebert panelguard series - type lpge, Active tracking filter series - type f – Liebert PanelGuard Extension User Manual

Page 14

Advertising
background image

Installation, Operation and Maintenance Manual

12

Liebert TVSS Units SL-22085 Rev 2, 11/2006

Surge Suppression Systems

Liebert PanelGuard Series - Type LPGE

Surge Protective Device (SPD)

Installation Instructions
1. Insure that all power is removed before beginning installation. A qualifi ed licensed electrician shall install all electrical

connections

2. The unit is provided in a NEMA 1 rated industrial-use enclosure and should be installed in areas only appropriate for NEMA 1.

3. The unit is to be wall mounted in an area where suffi cient access and working space around the cabinet can be assured. (See

NEC Section 110-16.) Position the SPD opposite the incoming feed to the panelboard. For example, if the panelboard is
supplied through the top of its enclosure, mount the SPD at the bottom of the panelboard.

4. Knockouts for connection of the suppressor to the panelboard back box are provided on top, bottom, and sides of the unit’s

enclosure. The diameters of the knockouts vary to accommodate conduit / collar diameters of 1/2 in. to 1 1/4 in. The proper
size busing (diameter and length) must be selected to protect the conductors as they transition from the SPD to the panelboard
conductor, and to maintain the cosmetic integrity of the Liebert LPGE Series Surge Protection Device.

5. When connecting the SPD to the panelboard, it is important that the panelboards interior and the SPD are protected from any

metal shavings, which may result. An inspection and cleaning of the LPGE should be performed before applying power.

6. Representative samples of this product have been investigated by Underwriters Laboratories, Incorporated to withstand,

without exposing live circuits or components at system voltages and fault currents of up to 200,000 AIC, as described in the
Standard for Safety, Transient Voltage Surge Suppressor (TVSS), Standard 1449, Second Edition, dated August 15, 1996.

7. An external circuit breaker is not necessary for over-current protection. However, it is recommended that the SPD be connected

in series with a 30A circuit breaker. The SPD shall be connected in accordance with all national and local electrical codes.

8. To obtain the suppression voltage ratings (SVRs), as obtained by Underwriters Laboratory, Incorporated, in accordance with

the Standard for Safety, Transient Voltage Surge Suppressors (TVSS), Standard 1449, Second Edition, dated August 15, 1996,
marked on this product, #8 AWG wire must be utilized to connect the unit to your facilities power grid. Connections made
with conductors other that #8 AWG may result in different SVRs.

9. Connect black wires (line or phase) marked L1/A, L2/B or L3/C, the white wire (neutral) marked N, and the green wire (ground)

marked G, of the SPD using the wire range listed in the table below in accordance with the National Electric Code (NEC) Article
285 and all local codes. To yield the best performance of the SPD within the electrical distribution system, keep all conductors
as short as possible and avoid sharp bends.

10. Connection to the Form ‘C’ contacts shall be with #18 – 22 AWG. Contacts are rated 5 amps at 250 VAC maximum with a

power factor of 1.0.

11. Apply power. The surge protector is fully operational when the GREEN LEDs are illuminated. If the GREEN LEDs are extinguished,

check to ensure that power is applied to the SPD. If an abnormal indication is present, remove power to the SPD and contact
Liebert/Emerson Network Power Surge Protection at 1-800-288-6169 or 1-607-724-2484.

12. Periodically monitor the status of the LEDs. Reduced protection exists if the GREEN LEDs are extinguished. Please contact

Liebert/Emerson Network Power Surge Protection at 1-800-288-6169 or 1-607-724-2484.

13.

The protection modules in these SPDs are replaceable, contact Liebert/Emerson Network Power Surge Protection
for replacement.

Dimensions (Inches)

Weight

A

B

C

Lbs

Kg

FxxxD800

Three Phase Delta

60.0

48.0

12.0

500

227

FxxxY800

Three Phase Wye

60.0

48.0

12.0

530

241

FxxxD1200

Three Phase Delta

60.0

48.0

20.0

700

318

FxxxY1200

Three Phase Wye

60.0

48.0

20.0

750

340

FxxxD2000

Three Phase Delta

60.0

48.0

20.0

875

397

FxxxY2000

Three Phase Wye

60.0

48.0

20.0

950

431

FxxxD4000

Three Phase Delta

60.0

48.0

20.0

1175

533

FxxxY4000

Three Phase Wye

60.0

48.0

20.0

1300

590

NOTE: Consult factory for special instructions on caseless and switchgear models.

Current

Model

Dimensions

(Inches)

Weight

Rating

XXX = VOLTAGE

Application

A

B

C

D

E

F

Lbs

Kg

FxxxN/L30 Single

Phase

24.0 20.0 9.0

21.25 10.0 .44

35 15.9

FxxxS30

Split

Phase

24.0 20.0 9.0

25.25 14.0 .44

45 20.4

FxxxD30

Three Phase Delta

24.0

20.0

9.0

25.25

14.0

.44

50

22.7

FxxxY30

Three Phase Wye

24.0

20.0

9.0

25.25

14.0

.44

60

27.2

FxxxN/L60 Single

Phase

24.0 20.0 9.0

21.25 10.0 .44

35 15.9

FxxxS60

Split

Phase

24.0 20.0 9.0

25.25 14.0 .44

45 20.4

FxxxD60

Three Phase Delta

24.0

20.0

9.0

25.25

14.0

.44

50

22.7

FxxxY60

Three Phase Wye

24.0

20.0

9.0

25.25

14.0

.44

60

27.2

FxxxN/L100 Single

Phase

30.0 24.0 9.0

25.25 14.0 .44

60 27.2

FxxxS100

Split

Phase

30.0 24.0 9.0

31.25 18.0 .44

70 31.8

FxxxD100

Three Phase Delta

30.0

24.0

9.0

31.25

18.0

.44

70

31.8

FxxxY100

Three Phase Wye

30.0

24.0

9.0

31.25

18.0

.44

80

36.3

FxxxN/L225

Single Phase L – N

30.0

24.0

9.0

25.25

14.0

.44

60

27.2

FxxxS225

Split

Phase

30.0 24.0 9.0

31.25 18.0 .44

70 31.8

FxxxD225

Three Phase Delta

30.0

24.0

9.0

31.25

18.0

.44

70

31.8

FxxxY225

Three Phase Wye

30.0

24.0

9.0

31.25

18.0

.44

80

36.3

FxxxD400

Three Phase Delta

48.0

36.0

12.0

49.25

30.0

.44

275

125

FxxxY400

Three Phase Wye

48.0

36.0

12.0

49.25

30.0

.44

300

136

Surge Suppression Systems

Installation, Operation and Maintenance Manual

17

Liebert TVSS Units SL-22085 Rev 2, 11/2006

Active Tracking Filter Series - Type F

Typical Cabinet Data (30 to 400Amps)

Typical Cabinet Data (800 to 4000Amps)

F

B

A

D

E

B

2.0” Max.

Large Bezel 2.0” Max. (Options)
Small Bezel .50” Max. (No Options)

A

C

12”

Application

30A

60A

100A

225A

400A

800A

1200A

2000A

4000A

Current

Rating

Model

XXX = VOLTAGE

Liebert Interceptor II Printer S14 14

12/29/06 1:38:00 PM