Installation, Operation and Maintenance Manual

14

Liebert TVSS Units SL-22085 Rev 2, 11/2006

Surge Suppression Systems

Connection
The AccuGuide assembly is provided in standard lengths of 5, 8, 10, 12, 15, and 20 feet. Each end of the assembly will include an
additional fi ve feet of #10, 8, 6, or 4 AWG pigtails for connection to the service and to the surge protective device (SPD). Gauge of
the pigtail is based on the SPD lug size. See chart below for units and acceptable wire ranges. An additional 10 gauge-grounding
conductor is provided with the AccuGuide assembly for use as an equipment ground.

Interceptor II Units

Acceptable Wire Range

All Units - No Disconnect

#14 – 2/O

SI016-025 – With Disconnect

#8 – 1/O

SI032-100 – With Disconnect

#14 – 2/O

Conduit
The AccuGuide assembly is sold without conduit. If conduit housing is required, the following conduit and fi tting sizes apply:

Equipment Performance
The ideal SPD installation locates the suppression as close to the protected bus as possible. This product was designed to address
those instances when a close installation is not possible. However, while the voltage drop experienced with an AccuGuide
assembly is signifi cantly reduced, care should be taken to keep connection lengths to a minimum.

Each end of the AccuGuide assembly is shipped with fi ve-foot pigtails. The length is offered as a worst-case need for the panel or
switchgear end (our SPD will be much less than 5 feet). We recommend cutting the pigtail to the shortest length possible.

No. of Conductors

Conduit Size (in.)

1 Coax Cable, 1 GND

1

2 Coax Cable, 1 GND

1-1/4

3 Coax Cable, 1 GND

1-1/4

4 Coax Cable, 1 GND

1 1/4

5 Coax Cable, 1 GND

1 1/2

6 Coax Cable, 1 GND

1 1/2

7 Coax Cable, 1 GND

1 1/2

Caution: Pigtails must be supported if pulling AccuGuide assembly through conduit. Grip only the blue coaxial cable
body when pulling the assembly through conduit. Do not pull AccuGuide assembly using the pigtails or damage
may occur.

LM Units

Acceptable Wire Range

All Units - No Disconnect

#14 – #2

LM060-080 – With Disconnect

#8 – 1/O

LM100-250 – With Disconnect

#14 – 2/O

Surge Suppression Systems

Installation, Operation and Maintenance Manual

15

Liebert TVSS Units SL-22085 Rev 2, 11/2006

Dimensional Information

Interceptor II Series - Type SI

E

F (4X)

B

A

D

C

1.840

Max.

Service Panel for

Loads to be Protected

Phase L1/A

Phase L2/B

Phase L3/C

Disconnect/Main

Breaker for

Panel
Neutral Buss

Ground Buss

Dedicated

Disconnect

(Optional)

Recommended Wire

Entrance

Summary Alarm Contacts (X2)

Pin 1 = Normally Open

Pin 2 = Common

Pin 3 = Normally Closed

TB1

TB2

1 2 3

1 2 3

Interceptor II, Type SI

Interceptor II, Type SI, with Rotary Disconnect

Unit

Dimensions (Inches)

Weight

(lbs)

Suggested

Breaker Size

Suggested

Wire Size

(AWG)

Allowable

Breaker

Range

Allowable

Wire Range

Dimensions (Inches)

Unit

Weight

(lbs)

Suggested

Breaker Size

Suggested

Wire Size

(AWG)

Allowable

Breaker

Range

Allowable

Wire Range

A

B

C

D

E

F

A

B

C

D

E

F

SI016
SI025
SI032
SI040
SI050
SI060
SI075
SI100

16

20

20

20

12

16

16

20

8

8

8

8

17.25

17.25

21.25

21.25

9.5

10

10

14

0.44

0.44

0.44

0.44

35

49

55

85

60 A

80 A

80 A

100 A

#6

#4

#4

#2

15A – 175A

15A – 175A

15A – 175A

15A – 175A

#14 – 2/O

#14 – 2/O

#14 – 2/O

#14 – 2/O

SI016
SI025
SI032
SI040
SI050
SI060
SI075
SI100

16

16

20

24

16

16

20

20

8

8

8

8

17.25

21.25

21.25

21.25

10

10

14

18

0.44

0.44

0.44

0.44

45

58

85

95

60 A

80 A

80 A

100 A

#6

#4

#4

#2

15A – 150A

15A – 175A

15A – 175A

15A – 175A

#14 – 1/O

#14 – 2/O

#14 – 2/O

#14 – 2/O

Liebert Interceptor II Printer S16 16

12/29/06 1:38:01 PM