Surge suppression systems, Typical parallel installations, Powersure low exposure series - type lpl – Liebert PanelGuard Extension User Manual

Page 23

Advertising
background image

Type LPM

Type ACV & AII

Type LPL

Installation Instructions

PowerSure Medium Exposure Series

AccuVar Series

PowerSure Low Exposure Series

1. Insure that all power is removed before beginning installation. A qualifi ed licensed electrician shall install all electrical

connections.

2. The SPD is provided in the enclosure type listed below. NEMA 12 enclosures are suitable for use in indoor installations. NEMA

3R, NEMA 4 or NEMA 4X enclosures are suitable for use in indoor or outdoor installations.

4. The SPD has obtained the short circuit current rating shown below.

Circuit Ampacity Limitations. Representative samples of these products have been investigated by Underwriters Laboratories,
Incorporated to withstand, without exposing live circuits or components at system voltages and fault currents of up to the rating
shown above, as described in the Standard for Safety, Transient Voltage Surge Suppressor (TVSS), Standard 1449, Second Edition,
dated August 15, 1996.

SPD

Mounting Hardware

SPD

Mounting Hardware

Type SI (Page 15)

3/8"

Type ACV/AII (Page 16)

#8

Type H (Page 16)

3/8"

Type LPM (Page 20)

#10

Type SS (Page 18)

1/4"

Type LPL (Page 21)

#6

Type LM (Page 19)

1/4"

SPD

Standard Enclosure

Optional Enclosures

SPD

Standard Enclosure

Optional Enclosures

Type SI

NEMA 4

NEMA 4X

Type ACV/AII

NEMA 4X

N/A

Type H

NEMA 12

NEMA 3R, 4, 4X

Type LPM

NEMA 12

NEMA 3R, 4, 4X

Type SS

NEMA 4X

N/A

Type LPL

ABS Plastic 94V-0

NEMA 1

Type LM

NEMA 12

NEMA 3R, 4, 4X

3. Determine where the SPD is to be mounted, allowing for minimum length of wire between itself and the input power terminals

of the service panel. Punch or cut the proper hole size in the side of the SPD closest to the knockout to be utilized in the service
panel. Drill mounting holes in wall at location picked for SPD next to service panel using mounting dimensions shown in the
tables on the “Dimensional Information” pages in this manual. Mount surge suppressor using the hardware listed.

SPD

Short Circuit Current Rating

SPD

Short Circuit Current Rating

Type SI

200,000 Symmetrical Amperes

Type ACV/AII

200,000 Symmetrical Amperes

Type H

200,000 Symmetrical Amperes

Type LPM

65,000 Symmetrical Amperes

Type SS

65,000 Symmetrical Amperes

Type LPL

14,000 Symmetrical Amperes

Type LM

200,000 Symmetrical Amperes

Installation, Operation and Maintenance Manual

8

Liebert TVSS Units SL-22085 Rev 2, 11/2006

Surge Suppression Systems

Typical Parallel Installations

Surge Protective Devices (SPD)

Interceptor II Series

Type SI

Hybrid Advantage Series

Type H

Type SS Series

Type LM Series

Surge Suppression Systems

Installation, Operation and Maintenance Manual

21

Liebert TVSS Units SL-22085 Rev 2, 11/2006

PowerSure Low Exposure Series - Type LPL

.188 (4X)

5.250

5.700

3.500

4.700

1/2” Offset

Conduit Nipple

Status

3.00 Max.

2.400

Status

Service Panel

for Loads to

be Protected

Phase L1/A

Phase L2/B

Phase L3/C

Disconnect/Main

Breaker for

Panel
Neutral Buss

Ground Buss

Dedicated

Disconnect

Unit is equipped with Summary

Alarm Contacts. The #18 wires

are designated as follows:

YELLOW = Normally Open
ORANGE = COMMON
BLUE = Normally Closed

Unit is supplied from the factory with a

minimum length of 18” of #12 wire for

connection. It is REQUIRED that a 30A circuit

breaker or less be used for installation.

Liebert Interceptor II Printer S10 10