Lennox Hearth Crestline LSBV-3628MN User Manual

Page 5

Advertising
background image

5

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

LENNOX HEARTH PRODUCTS • CRESTLINE™ SERIES B-VENT GAS FIREPLACES • 36"/42" LSBV MODELS • INSTALLATION INSTRUCTIONS

COLD CLIMATE INSULATION

For cold climate installations, seal all cracks

around your appliance with noncombustible

material and wherever cold air could enter

the room. It is especially important to insulate

outside chase cavity between studs and under

floor on which appliance rests, if floor is above

ground level. Gas line holes and other open-

ings should be caulked or stuffed with unfaced

fiberglass insulation.

If the fireplace is being installed on a cement

slab in cold climates, a sheet of plywood or

other raised platform can be placed underneath

to prevent cold transfer to the fireplace and into

the room. It also helps to sheetrock inside

surfaces and tape for maximum air tightness

and caulk firestops.

MANUFACTURED HOUSING

B-Vent Fireplaces are not approved for use in

OEM or aftermarket manufactured housing built

to HUD standards.

LOCATION

In selecting the location, the aesthetic and

functional use of the appliance are primary

concerns. However, vent system routing to

the exterior and access to the fuel supply are

also important.

Due to high temperatures, the appliance

should be located out of traffic and away from

furniture and draperies (Figure 3).

En raison des températures élevées,

l’appareil devrait être installé dans un endroit

où il y a peu de circulation et loin du mobilier

et des tentures (Figure 3).

The location should also be free of electrical,

plumbing or other heating/air conditioning

ducting.

Be aware that this is a heat producing ap-

pliance. Objects placed above the unit are

exposed to elevated temperatures.

Do not insulate the space between the appli-

ance and the area above it.

The appliance must be mounted on a fully sup-

ported base extending the full width and depth of

the unit. The appliance may be located on or near

conventional construction materials. However,

if installed on combustible materials, such as

carpeting, vinyl tile or other combustible material

other than wood flooring, the appliance shall be

installed on a metal or wood panel extending the

full width and depth of the appliance.

Typical Locations

Figure 3

Figure 5

Figure 4

Vertical Vent Termination Clearances

Termination Heights For Vents

Above Flat Or Sloped Roofs

Ref. NFPA 54 / ANSI Z223.1

Roof Pitch

* Feet

* Meters

Flat to 6/12

1.0

0.3

6/12 to 7/12

1.25

0.38

7/12 to 8/12

1.5

0.46

8/12 to 9/12

2.0

0.61

9/12 to 10/12

2.5

0.76

10/12 to 11/12

3.25

0.99

11/12 to 12/12

4.0

1.22

12/12 to 14/12

5.0

1.52

14/12 to 16/12

6.0

1.83

16/12 to 18/12

7.0

2.13

18/12 to 20/12

7.5

2.29

20/12 to 21/12

8.0

2.44

The vent / air intake termination clearances

above the high side of an angled roof is as

shown in the following chart:

Roof Pitch is X/12

12

X

Minimum Height from Roof

to Lowest Discharge Opening

VENT TERMINATION CLEARANCES

These instructions should be used as a

guideline and do not supersede local codes

in any way. Install venting according to local

codes, these instructions, the current National

Fuel Gas Code (ANSI-Z223.1) in the USA or

the current standards of CAN/CGA-B149.1

in Canada.

Vertical Vent Termination Clearances

Gas Vent Rule – Gas vent caps are not permitted

within 8 ft. (2.4 m) of a vertical wall or similar

obstruction.

Multiple Terminations

2 ft.

(0.6m)

Minimum

Gas vent caps that are located 8 ft. or more

from a portion of a building which extends

at an angle greater than 45° upward from the

horizontal may terminate in accordance with

Figure 4 , provided that in no case shall any

discharge opening on the cap be less than 2

ft. (.6 m) horizontally from the roof surface

(National Fuel Gas Code ANSI Z223.1 (NFPA

54) (CAN/CGA B149.1).

Multiple Terminations

These appliances may vent adjacent to and at

the same level with any other gas appliances

(including direct-vent appliances) provided that

there is at least 2 ft. (0.6m) between the proximal

edges of the vent caps. These appliances may

be vented adjacent to a chimney vent servicing

a solid fuel fireplace provided the B-vent cap

is at least 2 ft. (0.6m) away from the nearest

point of the chimney opening.

Advertising