NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Right Side of Fireplace

LENNOX HEARTH PRODUCTS • CRESTLINE™ SERIES B-VENT GAS FIREPLACES • 36"/42" LSBV MODELS • INSTALLATION INSTRUCTIONS

CLEARANCES

Minimum clearance to combustibles for the

appliance is as follows: sides and back - 3/8"

(9.52 mm), floor - 0" (0 mm), adjacent wall - 0"

(0 mm), ceiling - 37-1/2" (953 mm). Service

Clearances, Front - 3' (0.9 m).

NOTE: 3" (75 mm) minimum clearance is

required above any inclined vent component.

1" minimum clearance is required to the sides

of vertical vent.

Hearth Extension

- A hearth extension is not

required with this appliance. If a hearth exten-

sion is used, do not block the lower control

compartment door. Any hearth extension used

is for appearance only and does not have to

conform to standard hearth extension instal-

lation requirements.

Wall Finishes / Surrounds / Mantels

Note: Combustible wall finish materials and/

or surround materials must not be allowed to

encroach the area defined by the appliance front

face (black sheet metal). Never allow combus-

tible materials to be positioned in front of or

overlapping the appliance front face.

Non-combustible materials, such as surrounds

and other appliance trim, may be installed on

the appliance face with these exceptions: they

must not cover any portion of the removable

glass door (if used) or control compartment.

Vertical installation clearances to combustible

mantels vary according to the depth of the

mantel. See Figure 6. Mantels constructed of

non-combustible materials may be installed

at any height above the appliance opening;

however, do not allow anything to hang below

the fireplace hood.

Minimum clearance requirements include any

projections such as shelves, window sills,

mantels, etc. above the appliance.

NOTE: We recommend the use of high tem-

perature paint (rated 175° F or higher) on the

underside of the mantel.

To install the appliance facing flush with the

finished wall, position framework to accommo-

date the thickness of the finished wall (Figure

6). Both Figures 6 and 7 show a combustible

mantel shelf projecting a maximum of 12" (305

mm) from the wall, and which must be installed

a minimum distance of 12" (305mm) from the

top of the firebox opening. No other mantel

length/height combinations are allowable for

this fireplace.

Figure 7

60"

(1524 mm)

Min. to

Ceiling

12" Min.

(305 mm)

0" Clearance

to Combustible

Side Wall

Max. Projection 12" (305 mm)

Combustible

Mantel

Figure 6

Fireplace Opening

Typical Installation

10"

Min.

12"

Min.

18"

12"

Max.

Combustible

Mantel and Trim

(See Note)

3 Sheet Metal Screws

#10 x 3/4" Max. Flat Head

5"

Top Of Fireplace

Non

Combustible

Material

Sheet Metal

Spacer

Finished Wall

Header

Note: Mantel At Minimum Height Should Be Affixed to Framing Hinge Posts At Right

And Left Of The Fireplace. Do Not Use Molly Bolts In Front Of The Fireplace.

18 5/8"

Non-Combustible Material

1-3/8"

11-3/8"

Min.