Nailing Flanges

Four nailing flanges are provided to secure the

fireplace to the floor (see figure below). Bend

the nailing flanges down so that each flange is

flush with the floor, then using nails or screws,

secure the fireplace to the floor (2 places each

side). The heads of the screws or nails must

be large enough to completely cover the holes

in the nailing flanges.

Nailing Flange

(2 places each side)

Unbend to floor

and nail/screw

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

12

Figure 16

Insulated Chase Construction

Floor

Ceiling

Wall

• Must have the same firestopping

resistance as adjacent wall.

• Must have the same insulation as

adjacent ceiling.

• Follow local rules regarding framing

construction.

Attic Radiation

Shield

Roof Support

Storm Collar

Flashing

Drywall or Any Rigid

Material

2” x 4”

FIREPLACE

1/2” Plywood

Firestop

Insulate Joists

Same As Ceiling

Draft Stops

Firestop

CTDT

Termination

Note: Non-

Combustible

Chase

Flashing

Must Be

Used To

Cover

Chase

Opening

8'

Level

7’ 10”

(2.4 m)

Min.

7’ 6”

(2.3 m)

Min.

8’

(2.4 m)

Level

Outside

Base

Insulation

(Thermal Barrier)

Solid

Continuous

Surface

NOTE: It is recommended that the chase walls

and floor be insulated in the same manner,

using the same insulation, as the rest of the

building, below the attic.

SEE NOTE

Fireplace

Side

1. Combustible material must be installed flush

with the fireplace. It may not project in front

of and on the fireplace (i.e. the steel facade

of the fireplace) (see Figure 19).

2. Non-combustible materials such as brick,

stone or ceramic tile may project in front

of and onto the fireplace facing (see Figure

20).

IMPORTANT

The facade must be removable

once installed. The facade is

designed to overlap any facing

material installed on the front of

the fireplace. If thicker material

is installed, use the facade as a

template and make sure it can be

easily removed for servicing.

FACING

1

3

4

5

6

2

1

2

7

3

4

1. Fireplace

2. Front of fireplace

3. Wood frame (2” x 3” min)

4. Drywall

5. Tiles

6. Rock board or other

7. Brick

Fireplace Frame Section

(Top View)

Figure 17

MANTEL AND FACING

The mantel must be installed at least 59”

(1500 mm) above the base of the fireplace

(see Figure 18).