Lennox Hearth CAMBRIA 850 User Manual

Page 15

Advertising
background image

Figure 24

Figure 25

Aluminum Tape

Insulation

Blower

Tightening Collar

Flex 5” Diameter

Adaptor

Insulated

Flex Pipe

B) Attach the 5” flexible pipe, using the collars provided. Important: Make sure that the plastic

wrapping around the flexible pipe will not be in contact with the fireplace.

C) Route the flexible pipe to the chosen location. The ducting system can be installed either in an

upper room or in a lower room.

D) Attach the flexible pipe to the blower, using the collars (Figure 25).

E) Fix the back draft damper to the blower outlet.

F) Attach a flexible pipe to the fan / flexible pipe adapter (square to round) and stretch it up to the

location where the heat is required.

G) At that point, the flexible pipe can be attached to any air distribution grill.

H) Install the blower heating and cooling thermostat (HCTW) in that part of the house to be heated

by the hot air duct. The thermostat can be switched to a cooling thermostat and installed in

the same room as the unit. This thermostat will turn on the blower when the room where the

fireplace is located becomes too hot.

This option requires electricity. Make sure that the connections to the blower have been made ac-

cording to the local codes and comply with their requirements (see instruction provided with the

thermostat). For more information regarding central forced air kit, refer to the BISFWK-1 installation

sheet provided with the kit.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

15

The duct system must be installed respecting

the following:

1. Remove the plates closing up the 8” (203mm)

diameter holes on top of the fireplace. Then,

cut the insulation in order to obtain two 8”

(203mm) diameter openings. Fix the adap-

tors on the fireplace openings by turning

clockwise (see Figure 21).

2. Maintain at least a 2” (50 mm) clearance

between the ducts and any combustible

material; the required hole size is 13” x 13”

(330 mm x 330 mm).

Exception: For the grills, the framing

can be 10-3/4” x 10-3/4” (275 mm x

275 mm) to provide the clearance as

required by the integral spacers on the

double outlet duct system.

3. The maximum number of elbows in a run

of duct is two.

4. Maintain at least 6-1/2” (160 mm) clearance

from the outlet grill framing to a combustible

ceiling, side wall or mantel.

5. When traversing a combustible wall or floor,

a firestop must be installed at the wall or

floor penetration. The hole size must be 13”

X 13” (330 mm x 330 mm).

6. Do not connect the hot air ducts to a central

heating system. Malfunction of the heating

system’s fan will cause the fireplace to

overheat. A furnace duct is only single wall

and not double wall as is required for the

Cambria™ fireplace hot air exhaust.

7. Use only Lennox Hearth Products grills and

components as described in this manual.

Other grills or registers may be too restrictive

and may overheat the fireplace or ceiling.

8. Do not use insulated flexible ducts as they

will overheat.

9. Do not use tees or any other components

than the ones specifically listed here.

10. All ducts must extend upwards or horizon-

tally. Never route the ducting downwards.

11. The hot air outlet grills must be installed with

the louvers pointing downwards in order to

prevent overheating adjacent ceilings.

Central Forced Air Kit

The knock-outs provided on the back and on

the sides of the Cambria fireplace allow the con-

nection of insulated flexible pipe which enables

you to heat adjacent rooms up to 50 feet from

the fireplace hot air outlet.

The ducting system must be installed as de-

scribed below:

A) Fix the adaptor at the back and/or the side

of the fireplace by twist-locking the adaptor

to the fireplace. You can use more than one

outlet on the fireplace (see Figure 24).

Advertising
This manual is related to the following products: