Lennox Hearth CAMBRIA 850 User Manual

Page 17

Advertising
background image

Figure 28

THE CHIMNEY SYSTEM

Chimney Installation Notes

1. If possible, install an interior chimney as it will provide better perfor-

mance. In areas with continuous temperatures below 0°F (-18°C),

the use of an exterior chimney increases the likelihood of operating

problems such as low draft, high rate of creosoting, and poor start-up

characteristics. Exterior chimneys are also prone to down-drafting

and flow reversal. Installations which are located on lower floors in

the house, such as in a basement, in combination with an outside

chimney, are especially prone to flow reversal.

2. The Lennox Hearth Products fireplace model Cambria™ fireplace is

listed only with Security Chimneys International Ltd 10” dia. chimney

systems model Secure Temp

ASHT+

/ Nova Temp

HT6103+

or AC.

3. A chimney venting a fireplace shall not vent any other appliance.

4. The minimum chimney height is 15 feet (4.6 m) excluding the fire-

place.

5. All chimney installations must include at least one support in order to

be able to take any lateral load. The maximum chimney length that can

be supported by the fireplace is 12 feet (3.7 m) for Secure Temp

ASHT+

/ Nova Temp

HT6103+

and 26 feet (8m) for AC chimney. In altitude, add

18” (450 mm) to the chimney for every 2000 feet (600 m) above sea

level.

6. The chimney must extend at least 3 feet (915 mm) above its point of

contact with the roof and at least 2 feet (610 mm) higher than any

wall, roof or building within 10 feet (3m) of it (Figure 28).

7. If the chimney extends higher than 5 feet (1500 mm) above its point

of contact with the roof, it must be secured using a roof brace.

8. A rain cap must be installed on top of the chimney. Failure to install

a rain cap may cause corrosion problems.

9. Cut and frame square holes in all floors, ceilings, and roof that the

chimney will go through to provide a 2” (50 mm) clearance between

the chimney and any combustible materials. Do not fill this 2” space

with insulation or any other combustible material.

10. Portions of the chimney which may extend through accessible spaces

must be enclosed to avoid contact with combustible materials or

damage the chimney.

Ten (10) Feet

3.1 Meters

Three (3) Feet

.9 Meters

Minimum

Two (2) Feet

.6 Meters

Minimum

CHIMNEY MODEL

SqUARE HOLE

SIZE OPENING

Secure Temp

ASHT+

Nova Temp

HT6103+

16-3/8 in. (416 mm)

AC:

17 in. (432 mm)

Note: See Table 3 for Sloped Roof Framing

Table 2 - Flat Roof Framing

Figure 29 - Roof Framing

Note: 2" clearance to combustibles around chimney components re-

quired.

Note: Blown or fill type insulation materials must not be in contact with the

fireplace or in the enclosure frame as described in ‘’Enclosure’’ section.

Note: Local codes may not require firestopping at the ceiling levels for

outside chase installations. However, it is recommended for safety and

the reduction of heat loss.

CHIMNEY INSTALLATION INSTRUCTIONS

1. Cut and frame the holes in the ceiling, floor and roof where the chimney

will pass (see Figure 29). Use a plumb-bob to line up the center of

the holes. The sizes are indicated in Table 2 for the floor and ceiling

holes and Table 3 (Page 19) for the roof holes.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

17

Advertising
This manual is related to the following products: