Input wiring (tb1), Output wiring (tb3) – Liebert Nfinity 208 V / 240 V 60Hz User Manual

Page 17

Advertising
background image

15

Input Wiring (TB1)

To connect the input wiring, follow these steps:

1. Locate the

input wiring
access,
remove the
knockout
and pull the
three input
wires
through it,
allowing
some slack
for
installation.

2. Secure the conduit to the rear panel of the

UPS.

3. Input Power cables connect to screw

terminals on the Input Terminal Block
located to the right of the Bypass Voltage
Terminal. Connect the wires to the block
connections as shown below. Using a
torque wrench, turn the screws clockwise
until tightened to the proper torque value.
Insert the ground wire through the grounding
lug and tighten it to the proper torque value.

Grounding Conductor Installation

An insulated grounding conductor must be
identical in size, insulation material, and
thickness as the grounded and ungrounded
branch-circuit supply conductors. This cable
must be green with or without one or more
yellow stripes, and is to be installed as part of
the branch circuit that supplies the unit or
system.
The grounding conductor is to be grounded to
earth at the service equipment or, if supplied by
a separately derived system, at the supply
transformer or motor-generator set.

Output Wiring (TB3)

Output wiring may be configured one of two
different ways (240 / 120 or 208 / 120). Refer to
the chart and diagram below when configuring
the output wiring.

Note the Neutral / Ground jumper
on the terminal above.


Voltage

120

208

240

Terminals

1, 4
3, 4

2, 3

1, 3

Only use the connections listed above. Other connections
will produce non-standard voltages.


The

Nfinity UPS contains an isolation

transformer that generates a neutral
conductor for the connected equipment.
The UPS is a separately derived source
and contains a neutral to ground bonding
jumper. A grounding electrode conductor
(GEC) must be installed in accordance
with national and local wiring code /
regulations.

Advertising