6


The

Nfinity UPS is designed to operate as a true

on-line system in the following modes:

Normal Mode

The Power Module rectifiers derive power from a
utility AC source and supplies regulated DC
power to the inverter. The module’s inverter
regenerates precise AC power to supply the
connected equipment. The battery charger
maintains a float-charge on the battery.

Back-Up Mode

When AC utility fails, the connected equipment
is supplied power by the inverter, which obtains
energy from the battery modules. The output
power equipment will not be interrupted during
the failure or restoration of the AC utility source.

Auto Restart Mode

After a power outage and complete battery
discharge, once the AC utility is restored, the
UPS will automatically restart and resume
supplying power to the connected equipment.
This feature is enabled at the factory, but can be
disabled by the user. The user can also
program two auto restart delay settings:
1. Battery capacity level (%)
2. Countdown timer

Recharge Mode

When AC utility is restored, the unit will then
automatically recharge the battery modules until
they are fully charged.

Bypass Mode

The bypass provides an alternate path for power
to the connected equipment that operates in the
following manner:

Automatic

In the event of an internal failure or should
the inverter overload capacity be exceeded,
the UPS performs an automatic transfer of
the connected equipment from the inverter
to the bypass source.

Manual

Should the UPS need to be taken out of
service for limited maintenance or repair,
manual activation of the bypass will cause
an immediate transfer of the equipment from
the inverter to the bypass source.

Modes of Operation