Communication, Com ports, Intellislot™ ports – Liebert Nfinity 208 V / 240 V 60Hz User Manual

Page 19

Advertising
background image

17

COM Ports

Nfinity is able to communicate through multiple
communication ports simultaneously.

COM 1 – Relay Contacts

Relay contacts are available through a DB-9F
communications connector. Contact closure
provides the following:

Pin

Assignment

1

Low Battery (normally open)

4

UPS shutdown in battery mode
(5-12 V DC for 1.5 sec)

5

Common

7

Low Battery (common)

8

On Battery (common)

9

On Battery (normally open)

The contacts are rated 48V DC, 1 Amp
maximum and are compatible with the SiteNet
MultiLink software.

COM 2 – Serial

Nfinity is able to communicate via Liebert
proprietary protocol. The pin-out configuration
of the DB-9 connector is:

Pin

Assignment

2

Transmit Data

3

Receive Data

5

Common


Intellislot™ Ports

The following communication cards may be
used with

Nfinity:


Intellislot™ SNMP cards – allows the Nfinity
communicate intelligently with your Ethernet
network. The SNMP card must be installed in
port 1; any additional cards can be added in
consecutive ports.

Intellislot™ MultiPort4 cards– allows up to
four client computer systems to simultaneously
monitor the status of

Nfinity.


Intellislot™ Relay Contacts cards – provides
contact closures for remote monitoring of alarm
conditions; On Battery, On Bypass, Low Battery,
Summary Alarm, UPS Fault and On UPS
signals. It will integrate with AS400 computers
(additional cable required) and other monitoring
systems.