1

ZONE1 SHORT

Zone 1 short

Check for short in wiring of Zone 1.

2

ZONE1 OPEN

Zone 1 disconnection

Check for disconnection in wiring of Zone 1.

3

ZONE2 SHORT

Zone 2 short

Check for short in wiring of Zone 2.

4

ZONE2 OPEN

Zone 2 disconnection

Check for disconnection in wiring of Zone 2.

5

ZONE3 SHORT

Zone 3 short

Check for short in wiring of Zone 3.

6

ZONE3 OPEN

Zone 3 disconnection

Check for disconnection in wiring of Zone 3.

7

Reserved

8

Reserved

9

Reserved

10

Reserved

11

GROUND FAULT

Zone grounding

Grounding

12

PA SIGNAL FAULT

Power amplifier audio

Check the amplifier’s power amplifier circuit.

fault

13

CHECKING/SETTING

Speaker line check in

BUSY

progress

14

REFERENCE ERROR

Speaker line reference

There is a short or ground fault in one of the

value error

speaker lines. Identify the line in accordance with

the indicators or SURVEIL LANCE I/F, and check

for location of the short in the applicable line.

15

GND

GND

GND

16

PA TEMP FAULT

Power amplifier high

Check for a faulty fan, and check amplifier’s

temperature fault

power amplifier circuit.

17

COMM FAULT

Communication error

Check the amplifier’s internal wiring. Also

notification

check the Sound Message Unit for faults.

18

Reserved

19

Reserved

20

Reserved

21

GND

GND

GND

22

CLOCK ADJ CONT

Clock adjustment input

23

SP LINE REFERENCE

SP line reference

SETTING ACTIVATION

setting activation

24

SP LINE CHECK

SP line check

ACTIVATION

activation

25

GND

GND

GND

CONCEPT

SYSTEM

EXAMPLES

CONNECTIONS

PR

ODUCTS

BLOCK

D

IA

GRAMS

65

4

PRODUCTS

WU-ZS001E

CONCEPT

SYSTEM

EXAMPLES

CONNECTIONS

PR
ODUCTS

BLOCK

D

IA

GRAMS

64

4

PRODUCTS

WU-ZS001E

MAJOR OPERATING CONTROLS & TERMINALS

SURVEILLANCE I/F Connector Signals

Front of Unit

/DC OUT

T1AL

VOLTAGE

GND

SELECTOR

AC IN

SIGNAL

POWER

RM DC

STATUS

/SETTING

CHECK

SETTING

SP LINE

SURVEILLANCE I/F

5

ZONE

4

3

2

1

GROUND

FAULT

SP LINE FAULT

RED-SHORT
AMBER-OPEN

AMBER-NO SETTING
GREEN-SETTING COMPLETED

13

1

25

14

1 SURVEILLANCE I/F Connector
2 CHECK/SETTING Switch
3 SETTING STATUS Indicator
4 SP LINE FAULT ZONE 1-5 Indicators
5 SP LINE FAULT GROUND FAULT Indicator

Code

Indicator Condition

Meaning

Colour

Status

Amber

Lit

Reference value not set or abnormal

3

Amber

Flashing

Reference value setting operation in progress

Green

Lit

Speaker line check enabled (reference value set correctly)

Green

Flashing

Speaker line check in progress

Red

Lit

Speaker line is shorted (SHORT)

4

Amber

Lit

Speaker line is disconnected (OPEN)

Unlit

No speaker line short or disconnection

5

Red

Lit

Speaker line is grounded fault

Unlit

No speaker line grounding fault

Advertising