Connections and settings in torque control mode – Panasonic MINAS A3 Series User Manual

Page 23

Advertising
background image

153

[Connections and Settings in Torque Control Mode]

Connections and Settings in

Torque Control Mode

The motor decelerates and stops as the dynamic brake (DB) is

operated. The motor will be in free condition after it stops.

Free running, the motor decelerates and stops. The motor

will be in free condition after it stops.

In this case, if you shut off the main power during Servo ON, it

will be SERVO-OFF without a trip. Then, when the main pow-

er supply turns ON again, it will be recovered to Servo ON.

Shutting off main power during Servo ON will activate ab-

normal main power supply under-voltage (alarm code

No.13) and cause a trip.

65

0 – 1

Undervoltage

error response

at main power-off

The parameter sets whether to enable the “protection against main power
source under-voltage” function when you shut down the main power of
main and control power supplies.

Refer to the timing chart “At Power ON” of Preparations volume on page 40.

66

0 – 1

Dynamic breke

inhibition at

overtravel limit

The parameter sets driving conditions at decelerated operation after over-
travel input inhibit (CCWL: connector CN X5 9-pin or CWL: connector CN
X5 8-pin) has been activated and enabled.

Setting value

0

[1]

Main Power Source Under-voltage Protection Action

Setting value

[0]

1

Driving Conditions from Deceleration to Stop

Parameter

No.

Setting

range

Parameter Name

Unit

Function/Description

Default setting is shown by [ ]

67

0 – 7

Error response

at main power-off

The parameter sets:
(1) Driving conditions during deceleration and after stopping; and
(2) Processing to clear content of the deviation counter
after the main power source is shut off.

DB: Activation of dynamic brake

Setting

value

[0]

1

2

3

4

5

6

7

During Deceleration

DB

Free Run

DB

Free Run

DB

Free Run

DB

Free Run

After Stopped

DB

DB

Free

Free

DB

DB

Free

Free

Driving Conditions

Content of Deviation

Counter

Clear

Clear

Clear

Clear

Retention

Retention

Retention

Retention

68

0 – 3

Error response

action

The parameter sets driving conditions during deceleration or following
stop, after any of protective functions of the driver has been activated and
alarm has been generated.

(DB: Activation of dynamic brake)
See also “When Abnormality (Alarm) Occurs (Serve ON Command State)”
of the timing chart, Preparations volume on page 41.

Setting

value

[0]

1

2

3

During Deceleration

DB

Free Run

DB

Free Run

After Stopped

DB

DB

Free

Free

Driving Conditions

Content of Deviation

Counter

Clear

Clear

Clear

Clear

69

0 – 7

[0]

Sequence at

Servo-OFF

• The parameter sets:
1) Driving conditions during deceleration or after stop
2) Processing to clear the deviation counter
following Servo off (SRV-ON signal: CN X5 29-pin turns On ‡ Off).
• A relationship between setting of Pr69 and driving conditions/deviation

counter processing conditions is similar to that of Pr67 (Sequence at
Main Power Off).

• See also “Serve On/Off Operation When the Motor Stops” of the timing

chart of Preparations volume on page 42.