3 table of mewtocol−com error code – Panasonic FP2 User Manual

Page 47

Advertising
background image

Specifications

FP2−CCU

6 − 5

6.3

Table of MEWTOCOL−COM Error Code

6.3

Table of MEWTOCOL−COM Error Code

21 Data Error:

•

Situation
A data error occurred during communication.

There are three types of data errors: parity errors, framing errors, and unit

receive buffer errors.

•

Example of error
This occurs if the communication format between the host computer side

and the PLC side is different.

•

Precautions when the FP2 Computer Communication Unit is being
used

If the parity settings are different, the ERR LED lights but no error code is

returned.

•

ERR LED on the FP2 Computer Communication Unit
Lights

22 Overrun Error:

•

Situation
The CPU unit buffer is full, and no more data can be received.

•

Example of error
This occurs if a command being sent before a response has been

returned in cases such as commands being sent continuously from the

host side.

•

ERR LED on the FP2 Computer Communication Unit
Lights

24 Transmission Format Error:

•

Situation
There is an error in the setting of a hierarchy control command.

•

Example of error
This occurs if a hierarchy control command has not been notated

correctly.

•

ERR LED on the FP2 Computer Communication Unit
Lights

Advertising