Panasonic FP2 User Manual

Page 50

Advertising
background image

FP2−CCU

Specifications

6 − 8

6.3

Table of MEWTOCOL−COM Error Code

61 Data Error:

•

Situation
There is an error in the contact number and/or data number specification.

There is an error in the decimal or hexadecimal format specification for

the data.

•

Example of error
This occurs if the data register specification is in hexadecimal format

when an RD command is sent.

•

ERR LED on the FP2 Computer Communication Unit
Off

62 Registration Error:

•

Situation
Too many registrations have been entered, or a registration has not been

entered.

•

Example of error
This occurs if the number of data registered exceeds 16 words when an

MD command is sent.

•

ERR LED on the FP2 Computer Communication Unit
Off

63 PC Mode Error:

•

Situation
The PLC is in a mode in which the sent command cannot be processed.

•

Example of error
This occurs if the CPU unit side is in the RUN mode when a WR

command is sent.

•

ERR LED on the FP2 Computer Communication Unit
Off

65 Protect Error:

•

Situation
Write operation was performed to the program area or system register in

the memory protect state.

•

Example of error
This occurs if a password has been specified for the CPU when an RR

command is sent.

•

ERR LED on the FP2 Computer Communication Unit
Off

Advertising