Ex nA IIC T4 hazardous locations; and nonhazardous locations
only. Follow these guidelines if you are installing the NI 9426 in a
potentially explosive environment. Not following these guidelines
may result in serious injury or death.
Caution
Do not disconnect I/O-side wires or connectors
unless power has been switched off or the area is known
to be nonhazardous.
Caution
Do not remove modules unless power has been
switched off or the area is known to be nonhazardous.
Caution
Substitution of components may impair
suitability for Class I, Division 2.
Caution
For Zone 2 applications, install the system
in an enclosure rated to at least IP 54 as defined by
IEC 60529 and EN 60529.
Caution
For Zone 2 applications, install a protection
device that prevents the V
sup
voltage from exceeding
42 V if there is a transient overvoltage condition.