NI 9426 Operating Instructions and Specifications

Each channel has a DI pin to which you can connect a digital input
signal. The NI 9426 has four supply pins, V

sup

, that are internally

connected to the isolated reference of the module.

The NI 9426 has sourcing inputs, meaning the DI pin sources
current from V

sup

to the sinking output device. The NI 9426

internally limits current signals connected to DI. For more
information about input current levels, refer to the

Specifications

section.

You can connect 2-, 3-, and 4-wire sinking-output devices to
the NI 9426. A sinking-output device provides a path from the
DI pin to a voltage below V

sup

. An example of a sinking-output

device is an open collector NPN.

Connect the sinking-output device to the DI pin of the NI 9426.
Connect the positive power supply lead of the external device to the
V

sup

pin. Refer to Figure 2 for an illustration of connecting a device

to the NI 9426.