Overcurrent protection, Overcurrent protection -12 – National Instruments 6527 User Manual

Page 28

Advertising
background image

Chapter 3

Making Signal Connections

6527 User Manual

3-12

ni.com

The following equation shows the minimum sink current when V

OUT

is

0.5 V:

Figure 3-6. Signal Connections for Driving TTL Voltages

The maximum power ratings for the output channels on a 6527 device are
as follows:

Overcurrent Protection

The 6527 device outputs include circuitry to protect them from currents
over the specified range. When excessive current flows through the relay,
the relay increases resistance. Once the current level drops back under the
specified range, the relays return to normal operation.

Maximum DC voltage across the terminals (V

OUT

)

60 VDC

Maximum AC voltage across the terminals (V

OUT

)

30 V

RMS

(42 V

Peak

)

Maximum current (I

f

)

120 mA

1

1

With all relays carrying 120 mA and all inputs driven to 28 V, the total power dissipation

can approach 20 W. The maximum switching capacity in PCI and CompactPCI systems
must be derated according to the ambient temperature and cooling capacity of your system
to prevent the device from overheating. (The PXI chassis has built-in fans to handle 25 W
per slot.)

0.5V

35

------------

5V

0.5V

(

)

5 k

-----------------------------

13.4 mA

=

+5 V

R

L

= 5 k

V

OUT

Isolation

Isolated
Ground

Digital
Logic

390

To External +5 V Supply

I

f

35

6527

Advertising