Power supply installation

Standard 1.0

44

CallPilot

DC wire gauge tables

Introduction

The tables in this section specify the DC power feed wire requirements.

Cabinet and module DC feed recommended wire gauge
specifications

Notes:

1. Cabinet and module ground wire specification is #10 AWG insulated

green safety ground wire.

2. Cabinet conduit can be 1.91 cm (0.75 in.) or 3.18 cm (1.25 in.), and must

be insulated from cabinet ground.

Length

#10 AWG

#8 AWG

#6 AWG

Junction
box #4
AWG

Junction
box #4
AWG

0–30 m (100 ft)

yes

yes

yes

yes

yes

0–45 m (150 ft)

no

yes

yes

yes

yes

0–75 m (250 ft)

no

no

yes

yes

yes

0–135 m (450 ft)

no

no

no

yes

yes

0–210 m (700 ft)

no

no

no

no

yes

Over 210 m (700 ft) no

no

no

no

no