-48VDC power distribution rationale

„

Minimum installation is one Power Distribution Unit (PDU) with four
48VDC branch circuits fused at 20 amperes.

„

The customer must be able to shut off any branch, and every unit at the
site will continue to function properly.

„

DC-powered configuration fits into this scheme as follows:

„

Each PDU receives four branch circuits.

„

Each server receives a feed from each PDU and a different branch
circuit.

„

In this fashion, with dual hot-swappable power supplies, there is no
single point of failure in the power system. For example, you can remove
any power supply, including a PDU, and everything continues to work.

„

This is applicable to either North American or European installation sites
(with a 230 VAC Inverter).

„

The secondary rack supports four servers and follows a similar scheme.