Physical characteristics, Power requirements, Isolation voltage – National Instruments cFP-RTD-124 User Manual

Page 12: Environmental, Shock and vibration

Advertising
background image

FP-RTD-124 and cFP-RTD-124

12

ni.com

Physical Characteristics

Indicators .......................................... Green POWER and

READY indicators

Weight

FP-RTD-124 ............................... 140 g (4.8 oz)
cFP-RTD-124 ............................. 110 g (3.7 oz)

Power Requirements

Power from network module ............ 350 mW

Isolation Voltage

Channel-to-channel isolation ............ No isolation between

channels

Transient overvoltage........................ 2,300 V

rms

Environmental

FieldPoint modules are intended for indoor use only. For outdoor
use, FieldPoint modules must be mounted inside a sealed
enclosure.

Operating temperature ...................... –40 to 70 °C

Storage temperature .......................... –55 to 100 °C

Humidity ........................................... 10 to 90% RH,

noncondensing

Maximum altitude............................. 2,000 m

Pollution Degree ............................... 2

Shock and Vibration

Operating shock (IEC 68-2-27)

cFP-RTD-124.............................. 50 g, 3 ms half sine, 3 shocks;

30 g, 11 ms half sine,
3 shocks

Operating vibration, random (IEC 60068-2-34)

FP-RTD-124 ............................... 10–500 Hz, 2.2 g

rms

cFP-RTD-124 ............................. 10–500 Hz, 5 g

rms

Operating vibration, sinusoidal (IEC 60068-2-6)

[c]FP-RTD-124........................... 10–500 Hz, 5 g

Advertising