Figure 2. installing the cfp-rtd-124 – National Instruments cFP-RTD-124 User Manual

Page 3

Advertising
background image

© National Instruments Corp.

3

FP-RTD-124 and cFP-RTD-124

To install the cFP-RTD-124, refer to Figure 2 and complete the
following steps:

1. Align the captive screws on the cFP-RTD-124 with the holes

on the backplane. The alignment keys on the cFP-RTD-124
prevent backward insertion.

2. Press firmly to seat the cFP-RTD-124 on the backplane.

3. Using a number 2 Phillips screwdriver with a shank of at least

64 mm (2.5 in.) length, tighten the captive screws to 1.1 N

⋅ m

(10 lb

⋅ in.) of torque. The nylon coating on the screws

prevents them from loosening.

Figure 2. Installing the cFP-RTD-124

1

cFP Backplane

2

cFP Controller Module

3

cFP I/O Module

4

Captive Screws

5

Screw Holes

4

4

3

2

1

5

5