Connector Information

The I/O Connector Signal Descriptions and

RTSI Connector Pinout

sections contain information on M Series connectors. Refer to
Appendix A,

Device-Specific Information

, for device I/O connector

pinouts.

I/O Connector Signal Descriptions

Table 3-1 describes the signals found on the I/O connectors. Not all signals
are available on all devices.

Table 3-1. I/O Connector Signals

Signal Name

Reference

Direction

Description

AI GND

Analog Input Ground—These terminals are the input bias
current return point. AI GND and AO GND are connected on
the device.

Note: AI GND and AO GND are isolated from earth ground,
chassis ground, P0.GND, and P1.GND.

AI <0..15>

AI GND

Input

Analog Input Channels 0 to 15—For single-ended
measurements, each signal is an analog input voltage channel.
In RSE mode, AI GND is the reference for these signals.

For differential measurements, AI 0 and AI 8 are the positive
and negative inputs of differential analog input channel 0.
Similarly, the following signal pairs also form differential
input channels:

<AI 1, AI 9>, <AI 2, AI 10>, <AI 3, AI 11>, <AI 4, AI 12>,
<AI 5, AI 13>, <AI 6, AI 14>, <AI 7, AI 15>

Also refer to the

Analog Input Ground-Reference Settings

section of Chapter 4,

Analog Input

.

Note: AI <0..15> are isolated from earth ground and chassis
ground.

AO <0..1>

AO GND

Output

Analog Output Channels 0 to 1—These terminals supply the
voltage output of AO channels 0 to 1.

Note: AO <0..1> are isolated from earth ground and chassis
ground.