© National Instruments Corporation

3

cFP-2200/2210/2220

has the following symbol stamped beside it:

. Connect the backplane PE

ground terminal to safety ground using 14 AWG (1.6 mm) wire with a ring
lug. Use the 5/16 in. panhead screw shipped with the backplane to secure
the ring lug to the backplane PE ground terminal.

To ensure maximum cooling efficiency, mount the Compact FieldPoint so
that the I/O module vents are at the top and bottom, as shown in the
following figure:

Figure 2. cFP-22xx Installed on cFP-BP-4 Mounted Upright

Caution

Your installation must meet the following requirements for space and cabling

clearance:

Allow at least 51 mm (2 in.) all around the backplane for air circulation.

Allow 38 mm (1.5 in.) below and 51 mm (2 in.) above the controller.