Specifications

The following specifications are typical for a range of –40 to 70 °C
unless otherwise noted.

Output Characteristics

Number of channels.......................... 8

Output type ....................................... Sourcing

Output voltage .................................. Supply voltage – (Output

current

× Output impedance)

Supply voltage .................................. 5 VDC or 10 to 30 VDC,

user-provided

Maximum output current per channel

ON resistance

Revision E and later modules

1

... 0.15

Ω

Revision D and earlier
modules ...................................... 0.3

Ω

Pulse-width accuracy ........................ –1, +3

μs, any period and

duty cycle

Short-Circuit Protection

Minimum trip current

Revision E and later modules..... 9 A
Revision D and earlier
modules ...................................... 1 A

Module

Temperature Ranges

–40 to 50 °C

50 to 60 °C

60 to 70 °C

cFP-PWM-520

1 A

0.75 A

0.5 A

FP-PWM-520

1 A

1 A

1 A

1

The letter in the part number identifies the revision of the module. For example, part

number 185715A-02 identifies a revision A cFP-PWM-520. The part number is
printed on a label on the module. On the FP-PWM-520, the label is on the bottom of
the module. On the cFP-PWM-520, the label is on the back of the module.