Figure 3. wiring the [c]fp-pwm-520, Pulse-width modulator output circuit – National Instruments cFP-PWM-520 User Manual

Page 5

Advertising
background image

© National Instruments Corp.

5

FP-PWM-520 and cFP-PWM-520

Install a 2 A maximum, fast-acting fuse between the external
power supply and the V

SUP

terminal on each channel. Install

a 1 A maximum, fast-acting fuse suitable for the load at the
V

OUT

terminal. Figure 3 shows fuses where appropriate.

Figure 3. Wiring the [c]FP-PWM-520

Caution

M

aximum output current for the cFP-PWM-520

is lower than 1 A if the module is operating in the
50–70 °C temperature range. Refer to the

Specifications

section for more information, and select fuses for the V

OUT

terminals accordingly.

Pulse-Width Modulator Output Circuit

The [c]FP-PWM-520 output channels are optically isolated from
the rest of the FieldPoint bank. The channels are sourcing outputs
with short-circuit protection circuitry. Sourcing current means that
the V

OUT

terminal provides a path to a voltage supply. In the ON

state of the output period, a transistor is turned on between V

SUP

and V

OUT

. In the OFF state, this transistor is turned off, allowing

only a small leakage current to flow.

C V

V

SUP

V

OUT

[c]FP-PWM-520

COM

Protected

Sourcing

Output

+

Load

5 VDC or

10–30 VDC

External

Power Supply

COM

2 A Max

User-Supplied

Fuse

1 A Max

User-Supplied

Fuse

Advertising