Monitoring alert limits (green status leds), Monitoring accuracy, Alert relay specification – National Instruments Module NI PXI-8250 User Manual

Page 26: Connectors, Physical, Environment

Advertising
background image

Appendix A

Specifications

NI PXI-8250 User Manual

A-2

ni.com

Monitoring Alert Limits (Green Status LEDs)

Voltage rail level ....................................±5% (from nominal)

Intake temperature ..................................0–50 °C

Fan speed ................................................1,500 RPM or more for all fans

in a chassis

Monitoring Accuracy

Voltage rail level readings ......................±100 mV

Intake temperature readings....................±1 °C

Fan speed readings..................................±50 RPM

Alert Relay Specification

Max current (switching/carry) ................1 A

Max voltage ............................................30 V

Max power ..............................................30 W

Max cable length ....................................20 m

Connectors

Front panel connector .............................8-pin 3.5 mm pitch,

screw-flange connector

Physical

Front panel dimensions...........................3U

× 4 HP

Overall dimensions .................................13.34

× 2.03 cm (5.25 × 0.8 in.)

Weight ....................................................150 g (5.29 oz)

Environment

Maximum altitude...................................2,000 m (800 mbar)

(at 25 °C ambient temperature)

Pollution Degree .....................................2

Indoor use only.