Figure 1. install your module, Field wiring – National Instruments Quadrature Input Module FP-QUAD-510 User Manual

Page 3

Advertising
background image

© National Instruments Corp.

3

FP-QUAD-510

Figure 1. Install Your Module

Field Wiring

The terminal base provides connections for each axis and for an
external supply to power the FP-QUAD-510 input channels and
field devices.

The FP-QUAD-510 accepts two types of encoder signal inputs:
single-ended (TTL) or differential line driver. Figure 2 shows the
typical encoder wiring for differential signal input. Figure 3 shows
the typical encoder wiring for single-ended signal input. Power for
a +5 V encoder is also provided for each axis. If you require other
encoder power voltages, reference an external supply to either the
C terminal or the COM terminal.

Figure 2. Basic Field Connections to Differential Encoders

Alignment

Slot

Key

Latch

Guide Rails

Terminal Base

I/O Module

+A

–A

+B

–B

+Index

–Index

+5 V

GND

Encoder

+5 V

Reg

+

+A

–A

+B

–B

+I

–I

V

sup

COM

V

C