Table 1. terminal assignments, Status indicators, Figure 5. status indicators – National Instruments Quadrature Input Module FP-QUAD-510 User Manual

Page 5

Advertising
background image

© National Instruments Corp.

5

FP-QUAD-510

Terminal assignments and wiring diagrams are also listed under the
slide-in card on the front of the FP-QUAD-510 module.

Status Indicators

Figure 5 shows the module label and status indicators. Remove the
slide-in card to see wiring diagrams for the input signals.

Figure 5. Status Indicators

After you insert the module into a terminal base (and apply power),
the green POWER indicator lights and the FP-QUAD-510 informs
the network module of its presence. When the network module
recognizes the FP-QUAD-510, it sends initial configuration
information to the FP-QUAD-510. After receiving this initial
information, the green READY indicator lights and the
FP-QUAD-510 is in its normal operating mode.

Table 1. Terminal Assignments

Signal

Terminal Numbers

Axis 0

Axis 1

Axis 2

Axis 3

+A

1

5

9

13

–A

17

21

25

29

+B

2

6

10

14

–B

18

22

26

30

+I

3

7

11

15

–I

19

23

27

31

Vsup

4

8

12

16

COM

20

24

28

32

Advertising