Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace

18

INSTALLATION

RIGID PIPE VENTING ARRANGEMENTS - VERTICAL TERMINATIONS

(Propane & Natural Gas)

Vent must be supported at offsets

Maintain clearances to combustibles as listed on page 9.

Firestops are required at each fl oor level and whenever passing through a wall.

Must use optional rigid pipe adaptor when using rigid pipe vent systems (Part# 510-994).

The P121-1/P121LC-1/P121RC-1/P131-1 is approved for a maximum 35 ft. (10.7m) straight vertical, with rigid pipe vent systems for Propane
and Natural Gas, as per diagram 7 below.

Diagram 7

Straight Up Vertical Venting

Vertical Venting with One (1) 90

o

Elbow

Diagram 8

IMPORTANT

When installing this unit vertically, the 45

o

elbow when installed in conjunc-

tion with the Rigid Pipe Adaptor will pertrude past the unit 1-1/2" (38mm)
when measured from the rear standoffs.

Note: A 1-1/4" (32mm) clearance from the elbow must also be main-
tained.

Option

V

H

A)

1' (305mm) Minimum

2' (610mm) Maximum

B)

2' (610mm) Minimum

4' (1.22m) Maximum

C)

3' (914mm) Minimum

6' (1.86m) Maximum

D)

4' (1.22m) Minimum

8' (2.4m) Maximum

With the above options, maximum total pipe length if 37 feet with mini-
mum of 4 feet total vertical and maximum 8 feet total horizontal.
Please note minimum 1 foot between 90

o

elbows is required.