Installation, Minimum clearances to combustibles, Combustible mantel clearances – Regency L234-NG User Manual

Page 9: Inst alla tion

Advertising
background image

Regency

®

L234 Direct Vent Gas Insert

9

INST

ALLA

TION

INSTALLATION

MINIMUM CLEARANCES TO

COMBUSTIBLES


Side Walls

A 8" (203 mm)*

Ceiling

B 56" (1422 mm)

Min. Mantel Height C 21" (533 mm)

see Diagram 1

Max. Mantel Depth D 12" (305 mm)

see Diagram 1

Alcove Width

E 60" (1524 mm)

Alcove Depth

F 36" (914 mm)

Hearth Height

G 1-1/2" (38 mm)

Hearth Width

H 28" (686 mm)

Hearth Depth

I

12"

(305

mm)

* Alcove side wall must have a min. of 8" clearance.

COMBUSTIBLE MANTEL

CLEARANCES

Because of the extreme heat this fi replace emits, the mantel clear-
ances are critical.
Combustible mantel clearances from top of door frame
are shown in the diagram below. Mantel may be installed anywhere in the
shaded area or higher.

Note: A non-combustible mantel may be installed at a lower

height.

Note: Ensure the paint that is used on the mantel and the facing is

“heat resistant” or the paint may discolour.

Unless otherwise stated the clearances listed below are Minimum distances
to combustible materials. Please Note: A major cause of chimney
related fi res is due to a failure to maintain required clearances (air
space) to combustible materials. It is of the greatest importance
that this insert and vent system be installed only in accordance with
these instructions.

Faceplate

12” Min.

Hearth

Mantel

C

12" Max.

D

Existing or

Non-Combustible Hearth

Top of

Door Frame

G

INSTALLATION WITH NON-COM-

BUSTIBLE HEARTH IN FRONT

INSTALLATION WITH COMBUSTIBLE

FLOORING IN FRONT

Faceplate

Combustible

Flooring

Mantel

C

12" Max.

D

Top of

Door Frame

4” min

Diagram 1

No hearth required if the unit

is raised 4" (102mm) or more.