134

Using FINS Applications

Section 6-5

3. Starting FinsGateway ETN_UNIT Service

Select ETN_UNIT from Services under the Basic Tab in the FinsGateway
Setup Window, and then click the Start Button.

System Configuration Example 3: Connecting the CX-Programmer Online

Using the FINS/TCP Method

In this example, an online connection is made by FINS/TCP to a PLC on an
Ethernet network (PLC1 in the diagram below) from a CX-Programmer/CX-
Integrator connected to the Ethernet network.

Conditions

• FINS/TCP method

CX-Programmer's Change PLC Dialog Box

• Node address:

Set the remote FINS node address.

• IP address:

Set the remote IP address.

• Destination port number:

Set the FINS/TCP port number for the remote node.
Normally the PLC's default setting of 9600 should be
specified.

• Keep-alive setting:

Sets the keep-alive function. Normally this should be
selected.

CX-Programmer/CX-Integrator

Ethernet (Network number: none)

Ethernet port

Target: PLC1

Ethernet Unit

Node number: 1
IP address: 192.168.250.1

FinsGateWay Version 2003

IP address conversion: Automatic generation method (dynamic)
Ethernet Unit node number: 2
Ethernet Unit IP address: 192.168.250.2

FINS/TCP method

Settings for target PLC (PLC1)'s Change PLC Dialog Box

Setting

PLC name

PLC1

Network classification

FinsGateway

Network Tab

FINS destination

Network number

0

Node address

2

Frame length

2,000 bytes

Response monitor time

2 seconds