157

Socket Applications

Section 7-2

The MRES codes are shown in the following table along with the results they
indicate. Refer to 8-5 Troubleshooting with Response Codes for details on
response codes including the SRES.

7-2

Socket Applications

The format of the following FINS commands partially differs when the sockets
are used.

7-2-1

Format

The basic format of these commands is shown in the diagram below.

Command Code

Specifies the requested process.

Socket Option

For the TCP OPEN REQUEST (ACTIVE or PASSIVE), specifies whether or
not the keep-alive function is to be used. For all other commands it is dis-
abled. (Set to 0).

Socket Number

Specifies the socket number for which the process is requested, from 1 to 8.

Results Storage Area

Specifies the area to store the results of the requested process.

MRES

Execution results

00

Normal completion

01

Local node error

02

Remote node error

03

Unit error (controller error)

04

Service not supported

05

Routing error

10

Command format error

11

Parameter error

22

Status error

23

Operating environment error

25

Unit error

Command code

Name

Page

MRC

SRC

27

01

UDP OPEN REQUEST

167

02

UDP RECEIVE REQUEST

168

03

UDP SEND REQUEST

169

04

UDP CLOSE REQUEST

171

10

PASSIVE TCP OPEN REQUEST

172

11

ACTIVE TCP OPEN REQUEST

174

12

TCP RECEIVE REQUEST

177

13

TCP SEND REQUEST

178

14

TCP CLOSE REQUEST

180

Command
code

0

1

2

3

4

5

6

7

8

9

10

11

12

Socket option

Socket number

Results storage area

Parameters

Number of bytes from
the beginning of the frame