4 troubleshooting procedures, Troubleshooting procedures, Startup problems – Omron CS1W-ETN21 User Manual

Page 234: 4-1 startup problems

Advertising
background image

209

Troubleshooting Procedures

Section 8-4

8-4

Troubleshooting Procedures

The following procedures can be used to troubleshoot various problems in
system operation.

8-4-1

Startup Problems

RUN indicator lit?

Replace the Ethernet Unit.

Y

N

ERH indicator lit?

Y

N

ERC indicator lit?

N

Y

Power supplied

to CPU Unit?

Y

N

Ethernet Unit

loose on Rack?

N

Y

Do the RUN and ERH

indicators not light if another

CPU Unit is mounted

to the Rack?

N

Y

Is the same node

number used by another

Unit?

Y

N

Startup Problems occurred.

Make sure that sufficient
power is supplied to the
CPU Unit.

Make sure that Unit is firmly
mounted and tighten the
mounting screws firmly or
lock the sliders into place.

Replace the CPU Unit that
didn't work.

Create the I/O tables in
the CPU Unit.

Set the node numbers so that each one is used only once.

N

Y

N

Y

Y

N

Go to Network Connection Problems

ERH indicator not lit?

N

Y

N

Y

Set the unit numbers correctly.

Replace the Ethernet Unit.

Y

N

Is the node

address set between

01 and FE Hex?

Is the same unit

number used by another

CPU Bus Unit?

Has a CPU Unit error

occurred in the CPU Unit?

Restart the CPU Unit. If the error persists, replace the CPU
Unit.

Set the Unit Setup and routing tables
correctly.

ERH indicator not
flashing?

Is the IP address correct?

Correct the IP address in the System Setup, and read out the
controller status using the READ CONTROLLER STATUS
command in FINS communications and correct any problems
indicated.

Make sure that the node number and the last byte of the IP address are the same and set
other host IDs to 0, or change the address conversion method to use and IP address table
or combined methods.

Set the

node

address

to

between 01 and
FE Hex.