Network connection problems, 4-6 network connection problems – Omron CS1W-ETN21 User Manual

Page 244

Advertising
background image

219

Troubleshooting Procedures

Section 8-4

8-4-6

Network Connection Problems

Is the LNK indicator

lit?

Did all nodes

fail to respond to ping

command?

Is the twisted-pair

cable secured?

E

N

D

•

Firmly secure the cable.

•

Power may not be being supplied to the hub.

Y

N

Y

N

N

Did a particular

node fail to respond to

ping command?

•

The remote node may not support ICMP.

Y

N

Is the remote

node functioning as an

FTP client?

Y

N

Y

Only SD indicator
is flashing.

•

Connect by FTP.

Is the twisted-pair

cable between the Ethernet Unit

and the hub straight

cable?

•

Use straight cable.

N

Y

Network connection problem occurred.

Go through the procedure in
Startup Problems before
starting this procedure.

Execute the ping
command for all nodes
connected to the network.

•

Replace first the twisted-pair cable, then the hub,

and then the Ethernet Unit, in order.

•

The twisted-pair cable for that node may be

disconnected.

Execute FINS PROTOCOL
STATUS READ.

•

If the following parameters are counted, the corresponding

communications services may not be possible with the remote
node.
[IP status]

(2) (3) (5) (6) (All communications services)

[ICMP status] (5) (6) (7) (8) (ping)
[TCP status]

(3) reception status (4) (5) (6) (FTP, TCP sockets)

[UDP status]

(1) (2) (3) (FINS communications, UDP socket)

•

If the following parameters are counted, the load at the Ethernet

Unit may be too high. Adjust the user applications.
[IP status]

(4) (8) (9)