6 results storage area response codes, Results storage area response codes – Omron CS1W-ETN21 User Manual

Page 252

Advertising
background image

227

Results Storage Area Response Codes

Section 8-6

Network Relay Errors

For network relay errors using SEND(090) or RECV(098), check the path of
the command using the routing tables and the nature of the error using the
response code to eliminate the cause of the error.

For network relay errors using CMND(490), the location of the relay error is
recorded in the second through third words of the response, as shown below.

8-6

Results Storage Area Response Codes

The response codes stored in the Results Storage Area can be used to trou-
bleshoot socket service problems. Refer to Socket Services Parameter Area 1
to 8 (Ethernet Unit to CPU Unit)
on page 88 for the location of the response
codes stored in the Results Storage Area.

The UNIX socket service error messages corresponding to the response
codes are given in the following table. Refer to the documentation for the
devices involved when communicating between an Ethernet Unit and other
devices.

7

Bit

6

5

4

3

2

1

0

1

First byte

Command code

7

6

5

4

3

2

1

0

Second byte

First word

7

6

5

4

3

2

1

0

1: PLC non-fatal error flag

1: PLC fatal error flag

Relay error flag

1

7

6

5

4

3

2

1

0

S-b-response code (SRES)

Second word

Main response code (MRES)

7

6

5

4

3

2

1

0

1

7

6

5

4

3

2

1

0

Error node address

Third word

Error network address

Response

code

UNIX error

message

Description

Probable remedy

0003

ESRCH

No such process

Close the local socket and try reopening it.

0006

ENXIO

No such device or address

0009

EBADF

Bad file number (incorrect socket
specification)

000D

EACCES

Permission denied
(Broadcast address specified for
remote IP address for active TCP
open)

Check the IP address of the remote node and
try to reconnect.

000E

EFAULT

Bad address (copy failed between
kernel and user area)

Close the local socket and try reopening it.

0011

EEXIST

File exists

0016

EINVAL

Invalid argument (socket library
argument error)

0018

EMFILE

Too many open files (More than 32
sockets)

0020

EPIPE

Broken pipe (remote node closed
socket)

Close the local socket.

003C

EPROTONO-
SUPPORT

Protocol not supported (protocol
other than UDP, TCP, or RAW speci-
fied)

Close the local socket and try reopening it.

003D

EPROTOTYPE

Protocol wrong type for socket

003E

ENOBUFS

No buffer space available

There is too much load (traffic) on the Ethernet
Unit. Check your user applications.

Advertising