Hint, Precautions, 2 instructions – Omron SYSMAC CP CP1E-N@@D@-@ User Manual

Page 109

Advertising
background image

2-73

2 Instructions

CP1E CPU Unit Instructions Reference Manual(W483)

Tim

er and

Cou

nter

I

n

stru

ctio

ns

2

TMHH

/TMHH

X

• The setting range for the set value (SV) is 0 to 9.999 s for TMHH(540) and 0 to 65.535 for

TMHHX(552).

• The timer accuracy is -0.01 to 0 s.

Hint

The timer PV and timeup used in TMHH/TMHHX instructions are refreshed at the timing below.

Precautions

• Timer numbers are shared with other timer instructions. If two timers share the same timer number,

but are not used simultaneously, a duplication error will be generated when the program is checked,
but the timers will operate normally. Timers which share the same timer number will not operate prop-
erly if they are used simultaneously.

• The Completion Flag is updated only when TMHH(540)/TMHHX(552) is executed. The Completion

Flag can thus be delayed by up to one cycle time from the actual set value.

• The present value of a timer will not be refreshed even if the task is on standby.

• Timers will be reset or paused in the following cases. (When a timer is reset, its PV is reset to the SV

and its Completion Flag is turned OFF.)

*1

If the IOM Hold Bit (A500.12) has been turned ON, the status of timer Completion Flags and PVs will be maintained when
the operating mode is changed.

*2

The PV will be set to the SV when TMHH(540)/TMHHX(552) is executed.

• The present value of all operating timers will not be refreshed even if the timer is in a program section

that is jumped using JMP(004), CJP(510), JME(005).

• When TMHH(540)/TMHHX(552) is in a program section between IL(002) and ILC(003) and the pro-

gram section is interlocked, the PV will be reset to the SV and the Completion Flag will be turned
OFF.

• When a TMHH(540)/TMHHX(552) timer is forced set, its Completion Flag will be turned ON and its

PV will be set to 0. When a TMHH(540)/TMHHX(552) timer is forced reset, its Completion Flag will be
turned OFF and its PV will be reset to the SV.

• If online editing is used to overwrite a timer instruction, always reset the Completion Flag. The timer

will not operate properly unless the Completion Flag is reset.

Refresh timing

Description

When each instruction is executed

• The PV is updated every time that each instruction is executed.

• The timeup flag is ON when the PV is 0 and OFF otherwise.

Condition

PV

Completion Flag

Operating mode changed from RUN or MONITOR mode

to PROGRAM mode or vice versa.

*1

0

OFF

Power supply interrupted and reset

0

OFF

Execution of CNR(545)/CNRX(547), the RESET

TIMER/COUNTER instructions

*2

BCD: 9999
Binary: FFFF

OFF

Operation in interlocked program
section (IL(002)-ILC(003))

Reset to SV.

OFF

Operation in jumped program section

(JMP(004)-JME(005))

Retains previous
status.

Retains previous
status.